Installing a Chassis in a Rack or Cabinet

1
Use at least three screws on each end of each bottom-support rail.
Note
Step 3
Repeat Steps 1 and 2 to attach the other bottom-support rail to the rack.
Make sure that the two bottom-support rails are level with one another. If they are not level, adjust the higher
Note
rail down to the level of the lower rail.
What to do next
When the bottom-support rails are installed at the lowest possible RU and are level, you are ready to install
the chassis in the rack or cabinet.

Installing a Chassis in a Rack or Cabinet

To move a chassis to a rack, it is necessary to slide the chassis onto a mechanical lift. Use a mechanical lift
to position the chassis in front of its place on the rack. Slide the chassis from the lift to the rack. Then bolt
the chassis to the rack. You can make the chassis easier to move if you remove the power supplies, fan trays,
and fabric modules. Modules are sealed to minimize the chance of damage by electrostatic discharge (ESD).
You can remove modules from the chassis to make the chassis easier to move.
Before you begin
• You have fully installed a rack or cabinet (see
Cisco Nexus 9516 ACI-Mode Switch Hardware Installation Guide
22
Adjustable bottom-support
rails (2)
2
Installing a Rack or
Cabinet).
Installing a Chassis
M6 x 19-mm (or 12-24 x 3/4
in.) Phillips screws (at least
6 per rail)