Testing the XDP Alarm
Relays
5-12
To test the remaining six XDP alarm relays, access the setup menu as
described on page 5-4 and complete the following steps:
Range
Cal
Setup
4-20mA-Out
Alarms
Note: To configure the low and low low alarms, see the previous
section.
The following XDP alarm relays may be tested in this submenu:
Normal Alarm
XDP Fault Alarm
Gas Curve Relay 1 (see Appendix B for wiring instructions)
Gas Curve Relay 2 (see Appendix B for wiring instructions)
Process/Cal Relay (see Appendix B for wiring instructions)
Zero/Span Relay (see Appendix B for wiring instructions)
Testing of the "Normal Alarm" relay is used here as an example. Use
the same procedures to test any of the other alarm relays.
Alarms
Low-Low-Alarm
Normal-Alarm
XDP-Fault-Alarm
Alar..Normal-Alarm
Test
Alarms Norma..Test
Trip
Reset
Use the [ ] and [ ] keys to
[Alarms]
select
and press
[ENTER]
.
Use the [ ] and [ ] keys to
[Normal-Alarm]
select the
[ENTER]
testing, and press
If necessary, use the [ ] and
[Test]
[ ] keys to select
and
[ENTER]
press
.
Use the [ ] and [ ] keys to
[Trip]
[ENTER]
select
and press
Advanced Programming