Wiring the XDP

2-4
To completely wire the XDP, connect the following items:
analog output from transmitter (J6)
+24 VDC input to transmitter (J6)
XDP alarm relays (J3)
XDP analog output (J8)
serial port (J4) - optional
line power (J1)
Note: See Appendix B, Additional Wiring Connections, for a
discussion of connections to terminal blocks J2, J5, and J7.
Refer to the wiring diagram shown in Figure 2-2 on page 2-10, while
completing the instructions presented in this section.
!Attention European Customers!
To meet CE Mark requirements, install all cables as
described in Appendix A, CE Mark Compliance.
IMPORTANT:
The XDP requires an external power disconnect
device such as a switch or circuit breaker. The
disconnect device must be marked as such, clearly
visible, directly accessible, and located within 1.8 m
(6 ft) of the unit.
To ensure safe operation of the XDP, the unit must be
installed and operated as described in this manual. Also, be
sure to follow all applicable local safety codes and
regulations for installing electrical equipment. In addition,
all procedures should be performed by trained service
Remove the two side covers on the XDP enclosure. This is
accomplished by loosening the set screw in the cover and using a long
screwdriver or rod in the slots provided to unscrew the cover. Proceed
to the appropriate sub-section to wire each of the terminal blocks.
Note: A long, pin-like, plastic wiring tool is stored inside the XDP
enclosure. Insert the tool into the connector pin being wired to
open the hole, and then insert the wire. When the tool is
removed, the wire is clamped into the connector.
!WARNING!
personnel.