Advertisement

Owner's Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, oper-
ate or maintain the product described.
Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and / or property damage! Retain instructions for future reference.
Portable Air Conditioners
Descrip on
Weltem Portable Air Condi oners feature spot cooling for large areas
where cooling of the en re area is not prac cal. A dedicated spot cool-
ing thermostat controls the unit in this applica on.
These air condi oners can also be used in smaller areas for room cooling.
A control panel provides ease of use and contains a self-diagnos c func-
on and display, showing opera ng modes, room and set temperatures,
and faults.
If an abnormal opera on occurs, a visual display of the fault is shown.
Caster wheels are included for easy portability. Suitable applica ons in-
clude: a factory or work place, industrial kitchen, computer room, emer-
gency cooling, outdoor event, etc.
Unpacking
A er unpacking the unit, carefully inspect unit for any damage that may have occurred during
transit. Check for any loose, missing, or damaged parts.
Specifica ons
Model No.
Power Supply Ph-V-Hz
WPC-7000
Single Phase,
208 / 230V, 60Hz
WPC-9000
Model No.
WPC-7000
WPC-9000
Weight (Net / Gross)
Model No.
WPC-7000 216 / 234 lbs.(98 / 106 kg)
WPC-9000 253 / 271 lbs. (115 / 123 kg)
Owner's Manual
Cooling Capacity
28,000 / 29,000
36,000 / 37,000
Nema Plug
6-20p
6-30p
Condensate tank
Lbs(kg)
Power Con-
Btu/h
sump on Wa s
Power Cord
Power Cord
Gauge AWG
Length
12
10
No. of Cool Air
Gallons(Liters)
Outlets Pcs
3.17 (12)
1
WPC-7000 / 9000
WPC-7000 / 9000
WPC-7000/WPC-9000
Rated Cur-
rent Amps
3300
15.1/ 14.8
4400
20 / 19
Dimensions
W x H x D - in. (mm)
22.1 x 47.3 x 29.5
(560 x 1200 x 750)
10
26 x 54.3 x 34.8
(660 x 1380 x 885)
Ambient temperature
range °F( °C)
3
64~113 (18~45)
Figure 1
EER Btu/
Wh
9.3
10.6

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Icen WPC-7000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Weltem Icen WPC-7000

  • Page 1 Portable Air Conditioners Descrip on Weltem Portable Air Condi oners feature spot cooling for large areas where cooling of the en re area is not prac cal. A dedicated spot cool- ing thermostat controls the unit in this applica on.
  • Page 2: General Safety Informa On

    Owner’s Manual WPC-7000 / 9000 Specifica ons (Con nued) Se ng temperature Se ng temperature Model No. (Room cool mode) °F( °C) ((Spot cool mode) °F( °C) WPC-7000 64~86 (18~30) 32~86 (0~30) WPC-9000 Applica on Area Refrigerant Design Pressure - Model No.
  • Page 3 Owner’s Manual WPC-7000 / 9000 General Safety Informa on (Con nued) 10. DO NOT place any foreign objects on the unit. 11. DO NOT operate the unit with wet or damp hands. 12. DO NOT allow chemical substances to come into contact with the unit. 13.
  • Page 4 Owner’s Manual WPC-7000 / 9000 Assembly COMPONENT PARTS Figure 2 POWER CORD HOLDER TOP FAN EXHAUST FLANGE Figure 3 Figure 4 DISCHARGE DUCTS/SUPPLY AIR DUCT Figure 5...
  • Page 5: Moving The Unit

    Owner’s Manual WPC-7000 / 9000 Assembly (Con nued) AMBIENT AIR ADAPTER (Op onal) An ambient air adapter can be purchased separately. Air adapter fits over the condenser to duct condenser air to the unit to improve cooling ef- ficiency. 1. Remove air adapter from carton. 2.
  • Page 6: Control Panel

    Owner’s Manual WPC-7000 / 9000 Opera on CONTROL PANEL Figure 7 1. POWER BUTTON: Ac vates unit when POWER BUTTON is pressed. (Fan starts on low speed). If power bu on is pressed during opera on, unit stops. 2. BLOWER BUTTON: Changes fan speed from (Low) to (High) when pressed. 3.
  • Page 7: Maintenance

    Owner’s Manual WPC-7000 / 9000 Maintenance FILTER CLEANING (See Figures 8 and 9) There are two filters in the unit. The evaporator filter is located at the front of the unit. The condenser filter is located at the side of the unit. 1.
  • Page 8: Spring Replacement

    Owner’s Manual WPC-7000 / 9000 Maintenance (Con nued) – To ensure your product is covered by warranty, the complete faulty product along with your original purchase receipt must be provided at the place of purchase. Product Portable Air Condi oner Customer: Please read and keep this Model No.
  • Page 9 Owner’s Manual WPC-7000 / 9000 SELF-DIAGNOSTIC ALARM CODES Alarm Display Problem Cause Correc ve Ac on • Indoor heat • Do not use the air exchanger tempera- Frost preven on condi oner if ambient ture too low sensor and Abnormal temperature is lower •...
  • Page 10: Wiring Diagram

    Owner’s Manual WPC-7000 / 9000 Wiring Diagram RELAY RELAY DRAIN PUMP (option) Figure 11 - Circuit Wiring Diagram...
  • Page 11: Troubleshoo Ng Chart

    Owner’s Manual WPC-7000 / 9000 Troubleshoo ng chart Symptom Possible Cause(s) Correc ve Ac on High water level in con- 1. Remove blockage from drain densate tank hose Water leakage 2. Remove any object stuc un- deerneath of the black panel nuder the water tank 1.
  • Page 12 first write or call dealer from whom the product was purchased. Dealer will give addi onal direc ons. If unable to resolve sa sfactorily, write to Weltem at the address below, giving dealer’s name, address, date, and number of dealer’s invoice, and describing the nature of the defect. Title and risk of loss pass to buyer on delivery to common carrier.

This manual is also suitable for:

Icen wpc-9000

Table of Contents