Portable Air Conditioners
Descripti on
Weltem Portable Air Conditi oners feature spot cooling for
large areas where cooling of the enti re area is not practi cal.
A dedicated spot cooling thermostat controls the unit in this
applicati on.
These air conditi oners can also be used in smaller areas for
room cooling.
A control panel provides ease of use and contains a self-diag-
nosti c functi on and display, showing operati ng modes, room
and set temperatures, and faults.
If an abnormal operati on occurs, a visual display of the fault is
shown. Caster wheels are included for easy portability. Suitable
applicati ons include: a factory or work place, computer room,
emergency cooling, etc.
Unpacking
Aft er unpacking the unit, carefully inspect unit for any damage that may have occurred during
transit. Check for any loose, missing, or damaged parts.
Specifi cati ons
Model
Cooling Capacity
WPC - 5000P
21,100BTU ( 6.18Kw )
Depth / Width/ Height
Model
/ Weight
523 / 670 / 1042 (mm)
WPC - 5000P
/ 84kg
Refrigerant
Electrical supply
R32 (520g)
230V, 1phase, 50hz
Fan speeds
Air flow (high/low)
459 / 446 CFM
2
1
WPC-5000P
WPC-5000P
Figure 1
Rated Current
Power Consumption
Amps
Watts
9.07 A
2.07 kW
Noise level at 3m
Operating range
(high/low)
18~45°C
Below 70 dBA
WPC-5000P

Advertisement

loading
Need help?

Need help?

Do you have a question about the ICEN WPC-5000P and is the answer not in the manual?

Questions and answers

Summary of Contents for Weltem ICEN WPC-5000P

  • Page 1 / or property damage! Retain instructions for future reference. Portable Air Conditioners Descripti on Weltem Portable Air Conditi oners feature spot cooling for large areas where cooling of the enti re area is not practi cal. A dedicated spot cooling thermostat controls the unit in this applicati on.
  • Page 2 Owner’s Manual WPC-5000P “Original instructions” General Safety Information Please read this manual carefully for instructions on correct installation and usage. Please read all safeguards. 1. Transport and store the unit in an upright position only. Leave unit in an upright position for at least 3 hours before first use.
  • Page 3 Owner’s Manual WPC-5000P 19. DO NOT unplug the unit by pulling on the electrical cord. Keep electrical cord away from heat sources and always completely unroll the cord to avoid overheating. If the power cord be- comes damaged, a qualified service agent, qualified electrician, or similarly qualified person must replace it, in order to avoid a hazard or shock.
  • Page 4 Owner’s Manual Owner’s Manual WPC-5000P Assembly (WPC-5000P) Cool air outlet hose Top fan exhaust fl ange Display / Control board Evaporater / fi lter Condenser / fi lter tank Guide bar for condensate water Electrical access panel Condensate water tank (Water level is Power cord holder sensed, and the unit operati on is stopped when tank is full.
  • Page 5 Owner’s Manual Owner’s Manual WPC-5000P Installation WARNINGS REGARDING PROPER LOCATION FOR INSTALLATION Do not use the unit in explosive environments or in areas where flammable gas leakage may occur. Do not use the unit in areas where it will be exposed to rain or water. Do not use the unit in a corrosive atmosphere.
  • Page 6 Owner’s Manual Owner’s Manual WPC-5000P Operation CONTROL PANEL Figure 8 · Press the power button for 0.5 seconds to activate the product. · Press the power button for 0.5 seconds while driving to stop the product. · Self-diagnosis will be performed to test for abnormalities, after marking “VER”...
  • Page 7 Owner’s Manual WPC-5000P 1) Cooling mode (SPOTCOOL Mode) · The basic operation is based on “out” control. (discharge temperature TH1) · On/off the operation of the compressor. (COOL ↔ BLOWER) The set temperature cannot be changed and it operates which is set to ·...
  • Page 8 Owner’s Manual WPC-5000P 1) It is a mode that prevents the operation of the rest of the buttons except for power. - It can be operated and released by pressing for 2 seconds. ← ← Example Example of LOCK MODE of a set-up.
  • Page 9 Owner’s Manual Owner’s Manual WPC-5000P WPC-6000 Maintenance FILTER CLEANING (See Figures 9 and 10) There are two filters in the unit. The evaporator filter is located at the front of the unit. The condenser filter is located at the side of the unit. 1.
  • Page 10 Owner’s Manual Owner’s Manual WPC-5000P WPC-6000 Maintenance (Continued) – To ensure your product is covered by warranty, the complete faulty product along with your original purchase receipt must be provided at the place of purchase. Product Portable Air Conditioner Customer: Please read and keep this Model No.
  • Page 11 Owner’s Manual Owner’s Manual WPC-5000P WPC-6000 SELF-DIAGNOSTIC ALARM CODES Alarm Display Problem Cause Corrective Action • Do not use the air • Ambient temperature conditioner if ambient is too high temperature is higher Compressor • Unstable voltage than 45°C (113°F) overloaded supply •...
  • Page 12 Owner’s Manual WPC-5000P SELF-DIAGNOSTIC ALARM CODES Alarm Display Problem Cause Corrective Action TH1(Outlet) Abnormal tempera- temperature sensor Contact a qualified service ture sensor value has a loose or broken agent connection TH2(Inlet) Abnormal tempera- temperature sensor Contact a qualified service ture sensor value has a loose or agent...
  • Page 13 WPC-5000P 회로도 R-32 Owner’s Manual Owner’s Manual WPC-5000P WPC-6000 Wiring Diagram WPC-5000P (R-32) 50Hz Power Remote FLOAT Control (Option) SWITCH TIMER DOWN DRAIN BLOWER COOL POWER PUMP (Option) PRESSURE HIGH SWITCH PRESSURE (Option) SWITCH DIP SWITCH (Single Phase (1P)) (HP) (LP) OUT_TEMP DIP SWITCH (Three Phase (3P))
  • Page 14 Owner’s Manual WPC-5000P Troubleshooting chart Symptom Possible Cause(s) Corrective Action Position issue / Damage 1. Check the water tank is placed on the correct position Replace the damaged water tank with the new one. 2. Remove any object stuck underneath the Drain Pan underneath the water tank Water leakage FT sensor error...
  • Page 15 Owner’s Manual Owner’s Manual WPC-5000P Symptom Possible Cause(s) Corrective Action Compressor will not 1. Wait 3 minutes after unit is work if the unit is turned off before turning the turned off and on unit back on. quickly. 2. Check the Cool Icon If the light is off, A/C will be activated after light is on.
  • Page 16 Technical Advice and Recommendations, Disclaimer. Notwithstanding any past practice or dealings or trade custom, sales shall not include the furnishing of technical advice or assistance or system design. Weltem as- sumes no obligations or liability on account of any unauthorized recommendations, opinions or advice as to the choice, installation or use of products.