SERIES 300V
115 and 230 VOLT AC
FUEL TRANSFER PUMP
Owner's Operation & Safety Manual
Models FR300V, FR301V, FR310V &
SAFETY INSTRUCTIONS
To ensure safe and efficient operation, it is essential to read
and follow each of these warnings and precautions.
1. Improper use or installation of this product can cause serious
bodily injury or death.
2. Do NOT smoke near pump or use pump near an open flame
when pumping flammable fluids. Fire could result.
3. A Fill-Rite filter should be used on pump outlet to ensure that no
foreign material is transferred to fuel tank.
4. Use gasoline and oil resistant thread sealant or sealant tape on
all threaded joints to protect against leakage.
5. Storage tank should be anchored to prevent tipping in both the
full and empty conditions.
6. To minimize static electricity buildup, only use static wire,
conductive hose when pumping flammable fluids and keep
nozzle in contact with container being filled.
7. The pump motor is equipped with thermal overload protection. If
overheated, it will shut off without any damage to the windings.
Be sure to turn off the pump power if this occurs. When the
motor cools, it will restart without warning if power is on.
8. Take motors needing service to an authorized repair shop to
maintain "explosion proof" and "rain proof" integrity.
DANGER
Electrical wiring should be done by a licensed electrician in
compliance with local, state and national electric code NEC/ANSI/
NFPA 70, NFPA 30, NFPA 30A, as appropriate to the intended use
of the pump. Threaded rigid conduit, seal fittings and conductor seal
should be used. Pump should be properly grounded. Improper use
or installation of this product can cause serious bodily injury or
death.
WARNING
This product should not be used for fluid transfer into aircraft. This
product is not suited for use with fluids for human consumption or
fluids containing water.
INSTALLATION
GENERAL
Pumps are furnished with a tank adapter for skid tank mounting;
pedestals are available for island installations. All tanks must be
properly vented. A pressure retaining vent/fill cap can be used to
reduce fuel loss due to evaporation but will reduce flow rate.
Fill-Rite filters are recommended when pumping fuels.
Pump has a built-in check valve with pressure relief to prevent fluid
thermal expansion from causing unsafe system pressures. Do not
use additional check valves or foot valves unless they have
a proper pressure relief valve built into them.
check valves will reduce flow rate.
Use a gasoline and oil resistant pipe sealant on all pipe threads to
protect against leaks.
SKID TANK MOUNTING
1. Cut a 1-1/4" pipe that will extend to at least 3" above bottom of
tank when screwed into tank adapter and tank adapter is
screwed into tank flange.
2. Screw pipe into tank adapter, then screw tank adapter into tank
flange.
3. Mount pump on tank adapter.
FR311V
Additional
DIRECT MOUNTING TO UNDERGROUND TANK
1. Cut and thread both ends of a 2" pipe that will extend about 31"
above the ground when installed in tank flange.
2. Install this pipe in tank flange. Screw 2" standard pipe coupling
onto top of pipe.
3. Cut a 1-1/4" pipe that will extend to at least 3" above bottom of
tank when screwed into tank adapter and tank adapter is
screwed into 2" coupling.
4. Screw this pipe into tank adapter, then screw tank adapter into
2" coupling.
5. Mount pump on tank adapter.
ISLAND INSTALLATION
1. Install tank and piping per illustration.
2. The threaded 1-1/4" suction pipe is to extend 32-1/2" above
island.
3. Remove coupler from pedestal pipe by loosening set screws.
4. Slip pedestal pipe/pump base assembly over suction pipe.
5. Loosen screws in pump base to allow pedestal pipe to slide
down exposing end of suction pipe.
6. Screw coupler onto suction pipe.
7. Slide pedestal pipe into coupler, tighten set screws. Tighten
screws in pump base.
8. Mount pump on coupler.
ELECTRICAL
Pump motor voltage is factory set at 115 VAC. See diagram to
change voltage setting.
1. Install pump. Read and understand all the electrical wiring
instructions before proceeding.
2. Remove pump's electrical junction box cover and straighten the
wires to make the stripped wire ends accessible outside of the
junction box.
WARNING: AUX. WIRE IS LIVE WIRE! The AUX. lead wire is
insulated and enclosed when shipped. Do not connect this wire
without first verifying the 'ON' line voltage of the wire for
compatibility to the equipment to be installed. Maximum amperage
on wire is 1 ampere. The wire must be insulated and enclosed in
the junction box if not used.
3. Power to the unit should be supplied from a dedicated 30 amp
circuit breaker. No other equipment should be powered from this
breaker. Threaded rigid conduit, seal fittings and conductor seal
should be used. Provisions must be made to break both legs of
any AC circuit. Connect like colored pump wires to supply wires.
Ground wire must be connected.
4. Fold wires into junction box and replace cover making sure that
gasket is in place. Make sure screws are seated so there is no
space between the cover and the junction box.
OPERATING INSTRUCTIONS
1. Reset meter to 0 (if applicable).
2. Remove nozzle from nozzle boot and move switch lever up. This
will turn the pump on.
3. Insert nozzle into container to be filled. To minimize static
electricity buildup, keep nozzle in contact with container.
4. Operate nozzle lever to dispense fluid.
5. When desired amount of fluid has been dispensed, release
nozzle lever, remove nozzle from container, move switch lever
to down position to turn off pump, replace nozzle in boot.
TROUBLESHOOTING
IF PUMP FAILS TO PRIME: Check suction line for leaks or
obstructions.
Check bypass valve for dirt. The bypass poppet should slide
freely.
PUMP WILL NOT START: If motor hums but will not start, a
probable cause is a stuck rotor. Remove rotor cover; check rotor
and vanes for dirt. Also have an electrician check the electrical
power to the pump.
LOW PUMPING CAPACITY: Strainer screen clogged; bypass
valve not seated properly; obstruction in suction lines. Make sure
all 8 vanes slide easily in the rotor slots.

Advertisement

loading
Need help?

Need help?

Do you have a question about the FILL-RITE 300V Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tuthill FILL-RITE 300V Series

  • Page 1 DIRECT MOUNTING TO UNDERGROUND TANK 1. Cut and thread both ends of a 2" pipe that will extend about 31" above the ground when installed in tank flange. 2. Install this pipe in tank flange. Screw 2" standard pipe coupling onto top of pipe.
  • Page 4: Troubleshooting

    TROUBLESHOOTING PROBLEM POSSIBLE CAUSE SOLUTION Pump won't prime 1. Suction line problem Check for leaks in suction line 2. Bypass valve open Remove and inspect valve; must move freely & be free of debris 3. Vanes sticking Check vanes and slots for nicks, burrs and wear 4.
  • Page 5 The pumps are shipped with a threaded vacuum breaker installed. Fill-Rite recommends that the vacuum breaker be tubed back to the tank. The vacuum breaker is used to break a siphon should an open nozzle or a leaking hose be below the fluid level in the tank with the pump turned off.
  • Page 9: Localización De Fallas

    LOCALIZACIÓN DE FALLAS PROBLEMA CAUSA POSIBLE SOLUCIÓN La bomba no se ceba 1. Problema en la línea de aspiración Revise la línea de aspiración para verificar si hay fugas 2. Válvula de derivación abierta Extraiga e inspeccione la válvula; debe moverse libremente y estar libre de desperdicios 3.
  • Page 10 Utilice bujes reductores según sea necesario. CHECK VALVE STRAINER 8825 Aviation Drive Fort Wayne, Indiana USA 46809 Tel 260 747-7524 Fax 260 747-3159 www.tuthill.com...
  • Page 14: Dépannage

    DÉPANNAGE PROBLÈME CAUSE POSSIBLE SOLUTION La pompe ne s'amorce pas 1. Problème de conduite d'aspiration Chercher des fuites dans la conduite d'aspiration 2. Vanne de contournement ouverte Démonter et inspecter la vanne, elle doit bouger librement et ne pas être encombrée de débris 3.
  • Page 15 SOUPAPE CASSE-VIDE Les pompes sont livrées avec une soupape casse-vide filetée installée. Fill-Rite recommande que cette soupape soit connectée sur tube revenant au réservoir. La soupape casse-vide est utilisée pour arrêter un siphonage si une buse ouverte ou un tuyau fuyant sont plus bas que le niveau de fluide dans le réservoir avec la pompe arrêtée.
  • Page 19: Fehlersuche

    FEHLERSUCHE PROBLEM MOGLICHE URSACHE ABHILFE Pumpe lässt sich nicht vorfüllen 1. Problem in der Saugleitung Saugleitung auf Leckstellen untersuchen 2. Umgehungsventil offen Ventil ausbauen und kontrollieren, es muss sich frei bewegen lassen und schmutzfrei sein 3. Flügel klemmen Flügel und Nuten auf Kerben, Grate und Verschleiß kontrollieren 4.
  • Page 20 Tankpassstück verwendet wird, und der 1/4-Zoll-NPT-Anschluss nicht kann die Rohrleitung zu einer vorhandenen Öffnung auf der verwendet wird, diese Öffnung flüssigkeitsdicht verschließen. CHECK VALVE STRAINER 8825 Aviation Drive Fort Wayne, Indiana USA 46809 Tel 260 747-7524 Fax 260 747-3159 www.tuthill.com...