Download Print this page

M-system R3-NC1 Instruction Manual page 7

Cc-link interface module

Advertisement

■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
+0
15
+1
■ DISCRETE DATA (models: R3-DA16 and DC16, etc.)
15
0 : OFF
1 : ON
■ PLC REDUNDANT SYSTEM (models: R3-NC1-x/W)
Bit 0 of RY(n+1) is assigned to designate control system or standby system. Set this bit from the host PLC to switch from the
PLC master control system to the standby system, or vice versa. The R3 module output (slave station) is controlled according
to the bit combinations as shown in the table below. No switching is required for the R3 input modules which continuously
send out data to both 'main' and 'sub' network modules.
RY(n+1) 0 = 0 : PLC master control system
RY(n+1) 0 = 1 : PLC standby system
R3 MAIN (RY(n+1) 0)
0
0
1
1
• Operation
R3 main network
RY (n+1) 0 = 0
RY (n+1) 0 = 1
Communication Status
Start
(1)
R3 sub network
RY (n+1) 0 = 0
RY (n+1) 0 = 1
1) When the PLC master control/standby system bit is undefined due to no communication, the both host PLCs function as
'standby' system for each of R3 'main' and 'sub' network modules. All contact outputs are off, and analog output modules
output -15%.
2) The master PLC communicates with the R3 main network module, while the standby PLC communicates with the R3 sub
network module.
3) When a wire breakdown is detected at the R3 main network, the output signal is held for the preset time period (Timer is
programmable with the PC Configurator Software, R3CON). After the time has been elapsed, the output is switched from
the R3 main to R3 sub network. Be sure to set an appropriate output signal to the R3 sub network before the switching.
The host PLC for the R3 main network is now functioning as standby system.
4) Once the PLC control is transferred to the standby system, it is necessary to set RY(n+1) 0 = 1 to the R3 main network in
order to prevent R3 output control automatically switched to the main network when the R3 main network is restored. If
it is set to RY(n+1) 0 = 0, the R3 output will be switched to the main network even when the PLC control is in the standby
system.
5) When both R3 main and R3 sub network modules are in communication, the output can be switched without delay by set-
ting RY(n+1) 0 values. Be sure to set an appropriate output signal to the network module before the control is switched to
it.
0
Lower 16 bits
0
Higher 16 bits
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
Input 16 (Output 16)
R3 SUB (RY(n+1) 0)
0
1
0
1
Break
(2)
(3)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
:
CONTROL
Output from the 'main' network module.
Output from the 'main' network module.
Output from the 'sub' network module.
Hold the output
Restored
(4)
R3-NC1
Switching by PLC
(5)
EM-8355 Rev.15 P. 7 / 8

Advertisement

loading