Clearances to Combustible Material

The minimum clearances shown in the table below have been determined by tests according to
procedures set out in the safety standard ULC-S627-00 for Canada & UL-1482-2011 (R015) for USA.
Figure 3
A Back wall to stove rear
B Back Wall to connector pipe
C Side wall to stove side
D Side Wall to connector pipe
E Corner wall to stove corner
F Corner wall to connector pipe
Back Wall Exit Configuration
Figure 4
A Back wall to stove rear
B Back Wall to connector pipe
C Side wall to stove side
D Side Wall to connector pipe
G Ceiling to horizontal connector pipe
H Ceiling to floor
Minimum Clearance
Minimum Clearance
Single Wall
Double Wall
Connector
13" (330 mm)
10" (254 mm)
16.5" (419 mm)
13" (330 mm)
12" (305 mm)
12" (305 mm)
20.5" (521 mm)
20" (508 mm)
10.5" (267 mm)
6" (153 mm)
18.5" (470 mm)
13.5" (343 mm)
Single Wall
Connector
17" (432 mm)
20.5" (521 mm)
12" (305 mm)
20.5" (521 mm)
18" (457 mm)
82" (2083 mm)
Connector
Double Wall
Connector
10" (254 mm)
13" (330 mm)
12" (305 mm)
20" (508 mm)
16" (407 mm)
82" (2083 mm)