Wiring Procedures
Provided below is a Wire Block diagram for the ACS100 unit.
NOTE: The ACS100 has a pair of RS-485 wires for connecting an optional external OSDP Reader. The ACS100 can
support one wired lock with up to two readers (one internal and one optional external).
For the ACS100 unit to be used for controlling a door, make the following connections:
ACS100 Pigtail Wiring Description
Wire the REX & DOOR CONTACT (DC)
1.
Connect the Normally Open (NO) contacts of the REX device to the REX (Blue) and Ground
(Black) wires.
a)
2.
Connect the Normally Closed (NC) contacts of the Door Contact (DC) to the DC
(Yellow) and Ground (Black) wires.
a)
© 2020 Brivo Systems LLC. All rights reserved.
ACS100 Wire Block
When this switch closes, it initiates a Request-to-Exit (REX) program sequence, as
defined by the appropriate application, including the option to activate the door or
other relays, fire the door strike, and suppress any "Door Forced" messages.
In this context, an NC switch is considered closed when the door is closed (magnet is
present), and open when the door is open (no magnet is present).
12
P-MAN-PUB-Brivo ACS100 Installation Manual
Brivo ACS100 Installation Manual