SLAVE UPS Setting Procedure

!
NOTE
1. Before the UPS setting, install the metal cover plates for the UPS.
2. Keep door closed after the "MAINT" button located on the SW1 PCB (DPAU-89*) is pressed.
CAUTION
5-1. Supply the AC input and the Bypass input voltage to the UPS.
Initialization will start. Under initializing, the UPS will automatically:
- Turn on contactor CB1;
- Initialize converter operation;
- Initialize inverter operation;
After initialization, LCD screen should appear.
(See also: G9000 SERVICE MANUAL)
5-2. Press the "MAINT" button located on the SW1 PCB (DPAU-89*).
Maintenance screen will appear.
5-3. Press the "SETUP" tab on the Maintenance screen, then press the "INPUT PORT" button.
5-4. Press the "IN3" button, and select item "9: ANOTHER BUS. SYNC." by pressing"
1. As the "IN3" default setting, it may be "BATTERY TEMP. HIGH".
2. Before making a change of the "IN3" setting, make sure that the BATTERY TEMP. HIGH
(Contact Toshiba International Corporation, if BATTERY TEMP. HIGH function is under service.)
ATTENTION
5-5. Press the "OK" button, and confirm that "9: ANOTHER BUS. SYNC." is lay out.
5-6. Press the "MAINTENANCE" tab, then press the "MAIN MENU" button for completion of SLAVE UPS SETTING.
G9000 Series 1000kVA TOSHIBA SYNC KIT Installation Manual – 94471-001
The setting for MASTER UPS is not necessary.
function is defunct.