4-6. Connect the jumper wiring between the terminal 29 and 30 of TN13 on IOAU-19*.
A jumper wiring is not included in this KIT.
Terminal block:
WAGO CAGE CLAMP 236-404
Wire size:
AWG 28 - AWG 12
!
NOTE
8
Jumper (29 - 30)
Field installed
Figure 5-2 Installation of jumper wiring on IOAU-19*
A jumper wiring connection will vary based on input port setting.
See chapter "5 SLAVE UPS Setting Procedure" and also refer to
"G9000 SERIES INSTALLATION AND OPERATION MANUAL 480/480V
1000kVA" for details of input contacts.
G9000 Series 1000kVA TOSHIBA SYNC KIT Installation Manual – 94471-001