6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Loss
Low Line Comeback
Voltage
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Battery
Transfer
Inverter
Time
Inverter
EFFICIENCY
AC mode
Battery Mode
BATTERY
Type
Numbers
Standard
Model
Recharge Time
Charging Current
Charging Voltage
Type
Numbers
Long-run
Model
Charging Current
Charging Voltage
PHYSICAL
Dimension, D X W X H mm
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
10K
10KL
10000VA / 8000W
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
Bypass
ECO
> 89%
> 86%
12 V / 9 Ah
20
(18-20 adjustable)
1.0 A ± 10% (max.)
4.0 A ± 10% (max.)
592X250X576
83
28
Less than 58dB @ 1
Meter
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Power management from SNMP manager and web browser
15K
15KL
15000VA / 12000W
110 VAC(L-N) ± 3 % at 50% Load
176 VAC(L-N) ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC(L-N) ± 3 % at 50% Load
276 VAC(L-N) ± 3 % at 100% Load
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Three phase with ground
≧ 0.99 at 100% Load
208/220/230/240VAC
± 1%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 10min
110%~130%: 1min
>130% : 1sec
100%~110%: 30sec
110%~130%: 10sec
>130% : 1sec
3:1 max
0 ms
0 ms
<10 ms
>89%
>88%
12 V / 9 Ah
2 x 20
(18-20 adjustable)
9 hours recover to 90% capacity
2.0 A ± 10% (max.)
273 V ± 1% (Based on 20pcs batteries)
Depending on applications
18 - 20
8.0 A ± 10% (max.)
273 V ± 1% (Based on 20pcs batteries)
815X250
592X250
X826
X576
164
40
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m
Less than 60dB @ 1 Meter
44
20K
20KL
30K
20000VA / 16000W 30000VA / 24000W
>89%
>87%
12 V / 9 Ah
2 x 20
(18-20 adjustable)
(18-20 adjustable)
2.0 A ± 10% (max.) 4.0 A ± 10% (max.)
12.0 A ± 10%
8.0 A ± 10% (max.)
815X250
592X250
815 X 300
X826
X576
X 1000
164
40
234
Less than 65dB @ 1
30KL
>90%
>88%
3 x 20
(max.)
815X250
X 826
64
Meter