6. Specifications

Tower UPS
MODEL
CAPACITY
INPUT
Low Line Loss
Low Line Comeback
Voltage
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Phase
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Battery
Transfer
Inverter
Time
Inverter
EFFICIENCY
AC mode
Battery Mode
BATTERY
Type
Numbers
Standard
Model
Recharge Time
Charging Current
Charging Voltage
Type
Long-run
Numbers
Model
Charging Current
Charging Voltage
PHYSICAL
Dimension, D X W X H (mm)
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude*
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
*If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
**Product specifications are subject to change without further notice.
10K
10KL
10000VA / 9000W
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
Bypass
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
ECO
> 89%
> 86%
12 V / 9 Ah
20(18-20 adjustable)
1.0 A ± 10% (max.)
4.0 A ± 10% (max.)
815X250
592X250
X826
X826
109
38
Less than 60dB @
1 Meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
15K
15KL
15000VA / 13500W
110 VAC(Ph-N) ± 3 % at 50% Load
176 VAC(Ph-N) ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC(L-N) ± 3 % at 50% Load
276 VAC(L-N) ± 3 % at 100% Load
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Three phase with Neutral
≧ 0.99 at 100% Load
Three Phase with Neutral
3 x 400 VAC (3Ph+N)
± 1%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 10min
110%~130%: 1min
>130% : 1sec
100%~110%: 30sec
110%~130%: 10sec
>130% : 1sec
3:1 max
0 ms
<10 ms
>89%
>88%
12 V / 9 Ah
2 x 20(18-20
adjustable)
9 hours recover to 90% capacity
2.0 A ± 10% (max.)
273 VDC ± 1%
Depending on applications
18 - 20
4.0 A ± 10% (max.)
273 VDC ± 1%
815X250
592X250
X826
X826
164
40
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m
Power management from SNMP manager and web browser
34
20K
20KL
20000VA / 18000W
>89%
>87%
12 V / 9 Ah
2 x 20(18-20
adjustable)
2.0 A ± 10% (max.)
4.0 A ± 10% (max.)
12.0 A ± 10% (max.)
815X250
592X250
815 X 300
X826
X826
164
40
Less than 65dB @ 1 Meter
30K
30KL
30000VA / 27000W
>90%
>89%
12 V / 9 Ah
3 x 20(18-20
adjustable)
4.0 A ± 10% (max.)
815X250
X 1000
X 826
233.5
64

Advertisement

Table of Contents
loading

This manual is also suitable for: