1MRK 514 014-UUS A
Section 7
7.1
Identifying hardware and software version
Hardware and software version information can be found from the label that is attached on the
case of the IED. There is also module labels that can be used to identify modules inside the IED.
7.2
Checking mounting
Check that all fixing screws are tight and that all cables are connected.
7.3
Energizing the IED
Before you connect the auxiliary power, check that the terminal strip is wired and placed correctly.
During the start-up all LEDs are lit for a short period.
•
Green Normal LED starts to flash
•
LCD lights up and starting... is displayed
•
The main menu is displayed. A steady green Normal LED indicates a successful start-up.
If the IED detects a diagnostic error during start up, the green Normal LED flashes and the internal
fault code is displayed on the LCD.
Table 4:
Battery Supervision BATS
Station Battery
Active
Active
650 series
Installation manual
Checking installation
Supervision Power Supply
Output Ready
Active
Active
© Copyright 2011 ABB. All rights reserved
Logic
Led Battery
1
On
0
Off
0
On
0
Off
Checking installation
GUID-C5B48E09-7963-453C-B308-A52085B3F359 v1
GUID-50578D7B-23D4-45B0-BB10-D3108EEF9B97 v1
GUID-11B42B1B-A6EF-4A04-81B1-1305066621F1 v6.1.1
VS+ (output voltage)
VS+ Supervision
VS+ Output
> 15.1 V
> 33.5 V
< 14.6 V
> 33.5 V
> 15.1 V
< 32.9 V
< 14.6 V
< 32.9 V
Section 7
41