Huawei UPS5000-E-25 kVA-BF Quick Manual page 7

Table of Contents

Advertisement

Starting the Inverter
6.2
Battery Specifications
9 Ah/12 V
9 Ah/12 V
9 Ah/12 V
Initial Startup
a) Set parameters on the Settings Wizard screen. During setting, the Bypass mode and No
battery alarms do not need handling if they are triggered.
b) View the system running status diagram on the MDU to check that the UPS is working in
bypass mode.
c) Start the inverter on the app.
NOTE
If you do not need to use the app to start the inverter, choose System Info > Maintenance >
Inv. ON on the MDU.
The Service Expert app can be downloaded from Google Play and can run on Android.
The port number is 443 by default and can be modified. If the UPS is managed using the app,
the port number must be set to 443.
Number of Battery Strings
Connected in Parallel to the UPS
2
3
4
Battery Capacity
9 Ah + 9 Ah = 18 Ah
9 Ah + 9 Ah + 9 Ah = 27 Ah
9 Ah + 9 Ah + 9 Ah + 9 Ah = 36 Ah
Single/Parallel, Output frequency, Battery
capacity, and Number of cells must be
correctly set. Otherwise, the UPS running will
be affected.
Output voltage level refers to the line voltage.
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-50 kva-bfUps5000-e-75 kva-bfUps5000-e-75k-bf

Table of Contents