IFM AX460 Operating Instructions Manual
IFM AX460 Operating Instructions Manual

IFM AX460 Operating Instructions Manual

Multifunction displays for standard analogue signals

Advertisement

Quick Links

Operating instructions
Multifunction displays
for standard analogue signals
UK
AX460

Advertisement

Table of Contents
loading

Summary of Contents for IFM AX460

  • Page 1 Operating instructions Multifunction displays for standard analogue signals AX460...
  • Page 2: Table Of Contents

    Operating instructions AX460 Contents 1 Preliminary note � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4 1�1 Symbols and warnings used �...
  • Page 3 Operating instructions AX460 9�18 Display menu � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 38 10 Linearization �...
  • Page 4: Preliminary Note

    Operating instructions AX460 1 Preliminary note Technical data, approvals, accessories and further information at www�ifm�com� 1.1 Symbols and warnings used ► Instructions > Reaction, result […] Designation of keys, buttons or indications → Cross-reference Important note Non-compliance may result in malfunction or interference�...
  • Page 5: Safety Instructions

    Operating instructions AX460 2 Safety instructions ● The described unit is a subcomponent to be integrated into a system� The builder of the system is responsible for the safety of the system� It is the system builder’s responsibility to perform a risk assessment and to draft a documentation, in accordance with legislation and standard requirements, to be provided to the system operator and the system user�...
  • Page 6: 3�1 Product Features

    Operating instructions AX460 3.1 Product features: ● Multifunction device with operating modes for display of input 1 and input 2 and for linking of input 1 + input 2, input 1 - input 2, input 1 x input 2, input 1 : input ●...
  • Page 7: General

    Operating instructions AX460 Voltage spikes on the connections of the device are to be limited to the values of overvoltage category II� With regard to installation conditions, wiring, environmental conditions as well as screening and grounding of connected cables, the general standards for control cabinet construction in the machine industry as well as the manufacturer's specific screening instructions apply�...
  • Page 8: Dimensions And Mounting

    Operating instructions AX460 P_MZ_e200_0088 Original Scale Drawing (MTD) Function diagram 6 Dimensions and mounting ► Make a panel cut-out (91 x 43 mm) and fix the device into the panel with the 2 screws� EPS Source Product Scale Drawing Frame Size: 80 mm x 27 mm...
  • Page 9: Electrical Connection

    Operating instructions AX460 7 Electrical connection NOTE! ► Connect the IO-Link interface only after connecting the supply AN_i_AX460_GG Original Wiring Drawing (MTD) voltage� series DX204x DX2045 / DX2055 DX2043 / DX2053 DX20x2 / DX20x5 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Connections on the rear of the housing ³²%...
  • Page 10: 7�2 Auxiliary Voltage Output

    Operating instructions AX460 7.2 Auxiliary voltage output Auxiliary voltage for sensor supply is provided at terminals 3 and 4� The output voltage depends on the device supply: ● In case of DC device supply, the output voltage is approx� 1 V less than the supply voltage applied at terminals 1 and 2 and the max�...
  • Page 11: 7�5 Reference Output

    Operating instructions AX460 Connection of the control inputs Open control inputs are generally "LOW"� The input stages are designed for electronic control signals� Remark on mechanical switching contacts: If mechanical contacts are to be used as pulse source, a standard, external capacitor of about 10 μF must be connected to the terminals between GND (-) and...
  • Page 12: 7�6 Analogue Output (Dx2043, Dx2053)

    Operating instructions AX460 7.6 Analogue output (DX2043, DX2053) On terminals 13 and 14 / 15, a 16 bit analogue output is available� This output can be configured and scaled in the ANALOG MENU� The following configuration is possible: ● Voltage output: -10 … +10 V ●...
  • Page 13: 7�8 Ac Voltage Supply (Dx204X)

    Operating instructions AX460 7.8 AC voltage supply (DX204x) On terminals 24 and 25, the device can be supplied with an alternating voltage between 115 and 230 V AC� The power consumption depends, among other things, on the level of the supply voltage and the setting and is at approx� 3 VA plus the sensor current consumed at the auxiliary voltage output�...
  • Page 14: Operation / Touch Screen

    Operating instructions AX460 8 Operation / touch screen 8.1 Display for parameter setting The individual parameter menus and their parameters are described in a separate chapter (→ 9 Parameter / menu overview)� Device parameter setting: In order to be able to set device parameters, the touch screen must be pressed for 3 seconds�...
  • Page 15: 8�2 Display During Operation

    Operating instructions AX460 8.2 Display during operation The following displays are available� Depending on the device version and the selected operating mode, only certain visualisations are possible� The source (input 1, input 2, ���) for the one and two-line display and for the large display is defined in the DISPLAY MENU�...
  • Page 16: 8�3 Error Messages

    Operating instructions AX460 Display with quick-start function to enter the preselection values: In order to access the next display, you need to tap the top of the touch screen or tap SKIP� Only for DX20x2, DX20x3 and DX20x5� Display of the actual / min / max...
  • Page 17 Operating instructions AX460 Error message in the display Description ERROR: MIN� DOWN DISPLAY VALUE Lower display value of the two-line display is smaller than - 99 999 999� ERROR: MAX� LARGE DISPLAY VALUE Display value of the large display is greater than + 9999�...
  • Page 18: Parameter / Menu Overview

    Operating instructions AX460 9 Parameter / menu overview 9.1 Overview This section gives an overview of the individual menus and their parameters� The menu name is always in bold characters� The parameters belonging to the menu are arranged directly under the menu name� Default values are greyed out�...
  • Page 19 Operating instructions AX460 Menu / parameter Menu / parameter IN 2 TOTALIZATION PRESELECTION 1 MENU TIME BASE SOURCE 1 DIVIDER MODE 1 DECIMAL POINT HYSTERESIS 1 SCALE UNITS PULSE TIME 1 (S) OUTPUT TARGET 1 LINKAGE PROPERTIES OUTPUT POLARITY 1...
  • Page 20: 9�2 General Menu

    Operating instructions AX460 Menu / parameter Menu / parameter PRESELECTION 4 MENU COMMAND MENU SOURCE 4 INPUT 1 ACTION MODE 4 INPUT 1 CONFIG HYSTERESIS 4 INPUT 2 ACTION PULSE TIME 4 (S) INPUT 2 CONFIG OUTPUT TARGET 4 INPUT 3 ACTION...
  • Page 21: 9�3 In 1 Properties

    Operating instructions AX460 0000 Access not locked … 9999 Access after entering the PIN code 9999 PIN PARAMETER This parameter defines the PIN code for the locked access for all parameters (emergency PIN: 6079)� 0000 Access not locked … 9999 Parameter setting of the device is only possible after entering the PIN code�...
  • Page 22 Operating instructions AX460 DECIMAL POINT This setting defines the position of the decimal point� No decimal point 0000000�0 Decimal point at the specified spot 000000�00 Decimal point at the specified spot 00000�000 Decimal point at the specified spot 0000�0000 Decimal point at the specified spot 000�00000...
  • Page 23 Operating instructions AX460 gal/min Edit Unit With this parameter, a customer-specific unit with up to 16 digits can be edited� Open the "Edit Unit" menu with the [OK] button� Use the arrow keys to change the unit� Keep the arrow key pressed for fast scrolling� Save with [OK]�...
  • Page 24: 9�4 In 1 Linearization

    Operating instructions AX460 LINEARIZATION This parameter defines the linearization function (→ )� The linearization points are set in the IN 1 / IN 2 LINEARIZATION menu� No linearization 1 QUADRANT Linearization in the 1st quadrant 4 QUADRANT Linearization in all 4 quadrants TOTALIZATION This parameter activates the totalization function�...
  • Page 25 Operating instructions AX460 Totalizer Operating mode INPUT 1 TOTAL INPUT 2 TOTAL LINKAGE TOTAL IN 1 + IN 2 active active Total 1 + Total 2 IN 1 - IN 2 active active Total 1 - Total 2 IN 1 x IN 2...
  • Page 26: 9�6 In 2 Properties

    Operating instructions AX460 9.6 IN 2 Properties In this menu the parameters for output 2 are defined� CONFIGURATION Configuration of input 2 (→ 9.3 IN 1 Properties) START VALUE Display value of input 2 for an input signal of 0 V, 0 mA or 4 mA (→ 9.3 IN 1 Properties) END VALUE Display value of input 2 for an input signal of 10 V or 20 mA (→...
  • Page 27: 9�9 Linkage Properties

    Operating instructions AX460 DECIMAL POINT Position of the decimal point (→ 9.5 IN 1 Totalization) SCALE UNITS Unit indicated on the display (→ 9.5 IN 1 Totalization) 9.9 Linkage Properties In this menu the parameters for the linked operating mode are defined� This menu is only displayed if an operating mode with linking (e�g�...
  • Page 28: 9�10 Io-Link Properties

    Operating instructions AX460 9.10 IO-Link Properties In this menu, the parameters for the display of both output process data values can be defined This function is only available for the devices DX2045 and DX2055� IN1 FACTOR This parameter defines the factor with which the received value 1 is offset�...
  • Page 29: 9�11 Preselection Values

    Operating instructions AX460 9.11 Preselection Values In this menu, the preselection values and switching values are set� The preselection values / switch points always refer to the parameter SOURCE selected in the PRESELECTION MENU� This function is only available for the devices DX20x2, DX20x3 and DX20x5�...
  • Page 30 Operating instructions AX460 INPUT 1 TOTAL Source is input 1 with totalization INPUT 2 TOTAL Source is input 2 with totalization LINKAGE TOTAL The source is the result of the linking of input 1 and input 2 with totalization IO LINK VALUE 1...
  • Page 31 Operating instructions AX460 RESULT=PRES Display value equal to preselection 1� In combination with hysteresis 1 a frequency band (preselection +/- ½ hysteresis) can be defined and monitored� With hysteresis 1 not equal to 0 the following switching condition results: Display value > preselection 1 + ½ hysteresis 1 → OFF Display value <...
  • Page 32: 9�13 Preselection 2 Menu

    Operating instructions AX460 START UP DELAY 1 (S) Start-up delay for the switching condition of preselection 1� Time window until the monitoring function has been activated� This setting only applies for the switching conditions ¦RESULT¦≤¦PRES¦ and RESULT≤PRES. (Start-up delays 3 and 4 are set automatically.)
  • Page 33: 9�14 Preselection 3 Menu

    Operating instructions AX460 START UP DELAY 2 (S) Start-up delay for the switching condition of preselection 2 (→ 9.12 Preselection 1 Menu) (Start-up delays 3 and 4 are set automatically�) EVENT COLOR 2 Event-dependent colour change of the display for the switching condition of preselection 2, see Preselection 1 Menu 9.14 Preselection 3 Menu...
  • Page 34: 9�15 Preselection 4 Menu

    Operating instructions AX460 9.15 Preselection 4 Menu SOURCE 4 Source for preselection 4 (→ 9.12 Preselection 1 Menu) MODE 4 Switching condition for preselection 4, (→ 9.12 Preselection 1 Menu) (except tracking preset) see Preselection 1 Menu RES≥PRES-TRAIL Tracking preset 4: Display value greater or equal to preselection 3 –...
  • Page 35: 9�16 Analog Out Menu

    Operating instructions AX460 9.16 Analog Out Menu In this menu the basic settings for the analogue output are defined� This function is only available for the devices DX2043 and DX2053� ANALOG SOURCE This parameter defines the source for preselection for the analogue output�...
  • Page 36: 9�17 Command Menu

    Operating instructions AX460 +99999999 Highest possible final value ANALOG GAIN (%) With this parameter, the maximum gain can be set� The analogue gain indicates the maximum gain of the analogue output in % referred to +/- 10 V or 20 mA�...
  • Page 37 Operating instructions AX460 ACTIVATE N�A� STORE DATA N�A� TESTPROGRAM N�A� SET RED COLOR Display is red� The colour can be changed by means of the event-dependent colour change in the PRESELECTION 1 ��� 4 MENU� SET GREEN COLOR Display is green� The colour can be changed by means of the event-dependent colour change in the PRESELECTION 1 ���...
  • Page 38 Operating instructions AX460 9.18 Display menu Parameter changes are only active after quitting the menu selection� The totalization depends on the selected operating mode (→ 9.5 IN 1 Totalization)� START DISPLAY This parameter defines the start display after power-on of the device�...
  • Page 39 Operating instructions AX460 LINKAGE TOTAL The source is the result of the linking of input 1 and input 2 with totalization IO LINK VALUE 1 The PDout value 1 sent by the IO-Link master is the source for preselection IO LINK VALUE 2...
  • Page 40 Operating instructions AX460 INPUT 2 Source is input 2 LINKAGE 1 – 2 The source is the result of the linking of input 1 and input 2 INPUT 1 TOTAL Source is input 1 with totalization INPUT 2 TOTAL Source is input 2 with totalization...
  • Page 41 Operating instructions AX460 0�005 Minimum update time 0�1 Default value 9�999 Maximum update time FONT With this parameter, the font of the clear text can be selected� Standard Font 1 10 Linearization With this function, a linear input signal can be converted into a non-linear visualisation (or the other way round)�...
  • Page 42 Operating instructions AX460 Mode 1 Quadrant: Mode 4 Quadrant: P1(X) must be set to 0� Linearization is only defined P1(X) can also be set to negative values� With in the positive value range� measured values lower than P1(X) the value P1(Y) is constantly displayed�...
  • Page 43 Operating instructions AX460 11 Technical data Voltage supply (DC): Input voltage: 18 … 30 VDC Protection circuit: reverse polarity protection Current consumption: approx� 100 mA (without load) Protection: external: T 0�5 A Voltage supply (AC): Input voltage: 115 … 230 VAC (50 … 60 Hz)
  • Page 44 Operating instructions AX460 Control outputs: Number: (DX20x2, DX20x3, DX20x5) Format / level: 5 … 30 V (depending on the voltage on Com+), Output current: max� 200 mA Response time: < 1 ms IO-Link: IO-Link revision: 1�1 Type of transmission: COM3...
  • Page 45 Observe the safety instructions (→ 2 Safety instructions)� 12.4 Disposal ► Dispose of the device in accordance with the national environmental regulations� 13 Approvals/standards Test standards and regulations (→ 11 Technical data) EU Declaration of Conformity and approvals are available at www�ifm�com�...

Table of Contents