    Operating instructions FX460 Contents 1 Preliminary note � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4 1�1 Symbols and warnings used �...
  • Page 3 Operating instructions FX460 12 Maintenance, repair and disposal� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 47 12�1 Servicing�...
  • Page 4: Preliminary Note

    Operating instructions FX460 1 Preliminary note Technical data, approvals, accessories and further information at www�ifm�com� 1.1 Symbols and warnings used ► Instructions > Reaction, result […] Designation of keys, buttons or indications → Cross-reference Important note Non-compliance may result in malfunction or interference�...
  • Page 5: Safety Instructions

    Operating instructions FX460 2 Safety instructions ● The described unit is a subcomponent to be integrated into a system� The builder of the system is responsible for the safety of the system� It is the system builder’s responsibility to perform a risk assessment and to draft a documentation, in accordance with legislation and standard requirements, to be provided to the system operator and the system user�...
  • Page 6: 3�1 Product Characteristics

    Operating instructions FX460 3.1 Product characteristics: ● Multifunction device with operating modes such as speed sensor, counter, processing time display, position display, timer for operating times, stop watch or process display ● HTL pulse pick-up / sensor inputs with PNP, NPN or NAMUR inputs ●...
  • Page 7: General

    Operating instructions FX460 With regard to installation conditions, wiring, environmental conditions as well as screening and grounding of connected cables, the general standards for control cabinet construction in the machine industry as well as the manufacturer's specific screening instructions apply�...
  • Page 8: Dimensions And Mounting

    P_MZ_e200_0088 Original Scale Drawing (MTD) Operating instructions FX460 6 Dimensions and mounting ► Make a panel cut-out (91 x 43 mm) and fix the device into the panel with the 2 screws� AN_i_FX460_GG Original Wiring Drawing (MTD) 7 Electrical connection...
  • Page 9: 7�1 Dc Voltage Supply

    Operating instructions FX460 7.1 DC voltage supply The device can be supplied with direct voltage between 18 and 30 VDC via the terminals 1 and 2� The current consumption depends, among other things, on the level of the supply voltage and the setting and is typically at appr� 100 mA plus the sensor current consumed at the auxiliary voltage output�...
  • Page 10: 7�4 Control Inputs

    Operating instructions FX460 Namur Tri-State Open PNP inputs are generally "LOW" and open NPN inputs "HIGH"� The input stages are designed for electronic pulse pick-ups� Remark on mechanical switching contacts: If mechanical contacts are to be used as pulse source, a standard, external capacitor of about 10 μF must be connected to the terminals between GND (-) and...
  • Page 11: 7�5 Analogue Output (Dx2022, Dx2032)

    Operating instructions FX460 The input stages are designed for electronic control signals� Remark on mechanical switching contacts: If mechanical contacts are to be used as pulse source, a standard, external capacitor of about 10 μF must be connected to the terminals between GND (-) and the corresponding input (+)�...
  • Page 12: 7�7 Ac Voltage Supply (Dx2021, Dx2022, Dx2023)

    Operating instructions FX460 7.7 AC voltage supply (DX2021, DX2022, DX2023) On terminals 24 and 25, the device can be supplied with an alternating voltage between 115 and 230 V AC� The power consumption depends, among other things, on the level of the supply voltage and the setting and is at approx� 3 VA plus the sensor current consumed at the auxiliary voltage output�...
  • Page 13: 8�2 Display During Operation

    Operating instructions FX460 8.2 Display during operation The following displays are available� Depending on the device version and the selected operating mode, only certain visualisations are possible� Display with unit and status line: In order to access the next display, you need to tap the touch screen�...
  • Page 14: 8�3 Error Messages

    Operating instructions FX460 Display with quick-start function to enter the preselection values: In order to access the next display, you need to tap the top of the touch screen or "Skip"� Only for DX2022, DX2023, DX2032 and DX2033� Display with min / max value...
  • Page 15 Operating instructions FX460 Error message in the display Description ERROR: MIN� DOWN DISPLAY VALUE Lower display value of the two-line display is smaller than - 99 999 999� ERROR: MAX� LARGE DISPLAY VALUE Display value of the large display is greater than + 9999�...
  • Page 16: Parameter / Menu Overview

    Operating instructions FX460 9 Parameter / menu overview 9.1 Overview This section gives an overview of the individual menus and their parameters� The menu name is always in bold characters� The respective parameters are arranged directly under the menu name� Default values are greyed out� Depending on the device version and the selected operating mode only certain menus are displayed�...
  • Page 17 Operating instructions FX460 Menü / Parameter Menü / Parameter MODE VELOCITY PRESELECTION 3 MENU START / STOP SOURCE 3 DISPLAY VALUE MODE 3 BASE TIME (S) HYSTERESIS 3 DECIMAL POINT PULSE TIME 3 WAIT TIME (S) OUTPUT TARGET 3 STANDSTILL TIME (S)
  • Page 18: 9�2 General Menu

    Operating instructions FX460 Menü / Parameter Menü / Parameter COMMAND MENU LINEARIZATION MENU INPUT 1 ACTION P1(X) INPUT 1 CONFIG� P1(Y) INPUT 2 ACTION P2(X) INPUT 2 CONFIG� P2(Y) INPUT 3 ACTION ��� INPUT 3 CONFIG� P23(X) P23(Y) DISPLAY MENU...
  • Page 19 Operating instructions FX460 TRI-STATE Tri-State COUNTING DIRECTION With this parameter, it is possible to invert the rotational direction of the pulse input (only in the COUNTER A, B 90° operating mode)� FORWARD REVERSE Down SCALE UNITS This parameter defines which unit is indicated on the display� It does not influence the display value� The decimal point for decimal places is set with the DECIMAL POINT parameter�...
  • Page 20 Operating instructions FX460 inch/min Edit Unit With this parameter, a customer-specific unit with max� 16 digits can be edited� Open the "Edit Unit" menu with the [OK] button� Use the arrow keys to change the unit� Keep the arrow key pressed for fast scrolling� Save with [OK]�...
  • Page 21: 9�3 Speed Mode

    Operating instructions FX460 FACTORY SETTINGS The factory settings are not loaded The factory settings are loaded (default values shown in grey) 9.3 Speed mode In this menu, you can define the operation as rotational speed display (RPM), tachometer or frequency measurement� In this operating mode, only input A is active or input A and input B with a phase shift of 90 °...
  • Page 22 Operating instructions FX460 WAIT TIME (S) This parameter defines the period duration of the lowest frequency i�e� the waiting time between two rising edges at which the device detects the frequency 0 Hz� Frequencies with a period duration that is longer than the set Wait Time are evaluated as frequency = 0 Hz�...
  • Page 23: 9�4 Process Time Mode

    Operating instructions FX460 AVERAGE FILTER Optional averaging or filter function to avoid display fluctuations with unstable frequencies� With the EXPONENTIAL FILTER setting the device uses an exponential function� The time constant T (63 %) corresponds to the number of the sampling cycles�...
  • Page 24 Operating instructions FX460 BASE FREQUENCY (HZ) Setting of the reference frequency in Hz for the above display value� Lowest value Default value 500000 Highest value SAMPLING TIME (S) The set value corresponds to the minimum measured time in seconds� The sampling time serves as a filter in case of irregular frequencies�...
  • Page 25: 9�5 Timer Mode

    Operating instructions FX460 AVERAGE FILTER Optional averaging or filter function to avoid display fluctuations with unstable frequencies� With the EXPONENTIAL FILTER setting the device uses an exponential function� The time constant T (63 %) corresponds to the number of the sampling cycles�...
  • Page 26 Operating instructions FX460 START / STOP Definition of the start / stop type of the time measurement COUNT AT A HIGH Time measurement is active as long as input A is "HIGH" COUNT AT A LOW Time measurement is active as long as input A is "LOW"...
  • Page 27: 9�6 Counter Mode

    Operating instructions FX460 TOTAL TIME SET VALUE A set/reset command (SET TOTAL TIME command, via control input) sets the total timer to the value set here� Parameter only visible if TOTAL TIME MODE parameter is activated� 000000:00 Lowest value (reset) …...
  • Page 28 Operating instructions FX460 DECIMAL POINT This setting defines the position of the decimal point� No decimal point 0000000�0 Decimal point at the specified position 000000�00 Decimal point at the specified position 00000�000 Decimal point at the specified position 0000�0000 Decimal point at the specified position 000�00000...
  • Page 29: 9�7 Velocity Mode

    Operating instructions FX460 BATCH / TOTAL SET VALUE A set/reset command (SET BATCH / TOTAL command, via control input) sets the batch counter / total counter to the value set here� Parameter only visible if BATCH / TOTAL MODE parameter is activated�...
  • Page 30 Operating instructions FX460 DECIMAL POINT This setting defines the position of the decimal point� No decimal point 0000000�0 Decimal point at the specified position 000000�00 Decimal point at the specified position 00000�000 Decimal point at the specified position 0000�0000 Decimal point at the specified position 000�00000...
  • Page 31: 9�8 Preselection Values

    Operating instructions FX460 9.8 Preselection Values In this menu, the preselection values / switch points can be set� The preselection values always refer to the source (SOURCE 1���4) selected in the PRESELECTION MENU� This function is only available for the devices DX2022, DX2023, DX2032, DX2033�...
  • Page 32 Operating instructions FX460 BATCH COUNTER The batch counter is the source� (Only visible in BATCH / TOTAL MODE with INCREMENT BATCH, DECREMENT BATCH or USE INPUTS ONLY being set)� TOTAL COUNTER The total counter is the source� (Only visible in BATCH / TOTAL MODE with TOTAL COUNTER being set)�...
  • Page 33 Operating instructions FX460 RESULT=0 Display value equal to 0 (standstill after standstill time), e�g� standstill monitoring� (Only in SPEED and PROCESS TIME operating modes�) RESULT≥ PRES->0 Set display to 0� (Only in the TIMER or COUNTER operating modes)� If the display value is greater than or equal to preselection 1, the display value is set to zero�...
  • Page 34 Operating instructions FX460 OUTPUT POLARITY 1 Switching status for the switching condition of preselection 1 ACTIVE HIGH Active "HIGH" ACTIVE LOW Active "LOW" OUTPUT LOCK 1 Latching for the switching condition of preselection 1 No latching Latching START UP DELAY 1 (S) Start-up delay for the switching condition of preselection 1�...
  • Page 35: 9�10 Preselection 2 Menu

    Operating instructions FX460 9.10 Preselection 2 Menu SOURCE 2 Source for preselection 2 (→ 9.9 Preselection 1 Menu) MODE 2 Switching condition for preselection 2, see Preselection 1 Menu (except tracking preset) See Preselection 1 Menu RES≥PRES-TRAIL Tracking preset 2: Display value greater than or equal to preselection 1 –...
  • Page 36: 9�12 Preselection 4 Menu

    Operating instructions FX460 OUTPUT TARGET 3 Assignment of an output for the switching condition of preselection 3, see Preselection 1 Menu OUTPUT POLARITY 3 Switching status for the switching condition of preselection 3, see Preselection 1 Menu OUTPUT LOCK 3...
  • Page 37: 9�13 Analogue Menu

    Operating instructions FX460 EVENT COLOR 4 Event-dependent colour change of the display for the switching condition of preselection 4, see Preselection 1 Menu 9.13 Analogue menu In this menu the basic settings for the analogue output are defined� This function is only available for the devices DX2022 and DX2032�...
  • Page 38: 9�14 Command Menu

    Operating instructions FX460 10000 Default value +99999999 Highest possible final value ANALOG GAIN (%) With this parameter, the maximum gain can be set� The analogue gain indicates the maximum gain of the analogue output in % referred to +/- 10 V or 20 mA�...
  • Page 39 Operating instructions FX460 SCROLL DISPLAY Display change CLEAR LOOP TIME All defined switching conditions enabled START PRESELECTION N�A� ACTIVATE N�A� STORE DATA N�A� TESTPROGRAM N�A� SET RED COLOR Display is red� The colour can be changed by means of the event-dependent colour change in the PRESELECTION 1 ���...
  • Page 40: 9�15 Display Menu

    Operating instructions FX460 INPUT 3 CONFIG This parameter defines the switching characteristics for the Ctrl� In 3 input� See activation assignment parameter INPUT 1 CONFIG� 9.15 Display menu Parameter changes are only active after quitting the menu selection� SOURCE DUAL TOP Source for the two-line display, 1st line MEASUREM�...
  • Page 41 Operating instructions FX460 COLOR This parameter defines the display colour� The colour can be changed by means of an event-dependent colour change in the Preselection 1 ��� 4 Menu� This event-dependent colour change is only available for the devices DX2022, DX2023, DX2032, DX2033�...
  • Page 42 Operating instructions FX460 DOUBLE WITH UNITS Two-line display with units (Only visible in counter configuration A+B or A-B and with batch counter, total counter or total timer being activated)� LARGE Large display (only if LARGE DISPLAY parameter is activated) COMMAND Display of the keyboard commands (Only visible in TIMER and COUNTER operating modes)�...
  • Page 43: 9�16 Linearisation Menu

    Operating instructions FX460 9.16 Linearisation menu In this menu the linearisation points are defined� Linearisation is only possible in the SPEED, PROCESS TIME and COUNTER operating modes� This menu is only displayed if the corresponding LINEARIZATION MODE is selected in the GENERAL MENU�...
  • Page 44 Operating instructions FX460 Mode 1 Quadrant: Mode 4 Quadrant: P1(X) must be set to 0� Linearisation is only defined P1(X) can also be set to negative values� With in the positive value range� measured values lower than P1(X) the value P1(Y) is constantly displayed�...
  • Page 45: Technical Data

    Operating instructions FX460 11 Technical data Voltage supply (DC): Input voltage: 18 … 30 VDC Protection circuit: reverse polarity protection Current consumption: approx� 100 mA (without load) Protection: external: T 0�5 A Voltage supply (AC): Input voltage: 115 … 230 VAC (50 … 60 Hz)
  • Page 46 Operating instructions FX460 Indication: Type: graphic LCD with backlight Display range 8 decades plus sign (-99999999 ��� +99999999) Character height 13 mm Colour: red / green / yellow (selectable) Operation: touch screen (resistive) Housing: Material: ABS, UL 94 V-0 Installation:...
  • Page 47 Observe the safety instructions (→ 2 Safety instructions)� 12.4 Disposal ► Dispose of the device in accordance with the national environmental regulations� 13 Approvals/standards Test standards and regulations (→ 11 Technical data) EC Declaration of Conformity and approvals are available at www�ifm�com�...