IFM VSP003 Operating Instructions
IFM VSP003 Operating Instructions

IFM VSP003 Operating Instructions

Acceleration sensor

Advertisement

Operating instructions
Acceleration sensor
UK
VSP003

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VSP003 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for IFM VSP003

  • Page 1 Operating instructions Acceleration sensor VSP003...
  • Page 2 • Protect units and cables against damage. 3 Functions and features The VSP003 acceleration sensor detects the vibration acceleration on non-rotating components and is suitable for connection to the VSE evaluation unit.
  • Page 3 4 Installation ► Mount only in a thick housing wall (e.g. transport thread). ► Ensure that the signal direction is correct. ► Ensure a safe vibration transmission and allow no elastic intermediate layers. 1: Tighten the sensor with a tightening torque of 8 Nm. 5 Electrical connection The unit must be connected by a qualified electrician.
  • Page 4 5.2 Use of a screened cable ► Use a screened cable to avoid conducted interference. ► Connect the screened cable to the DIN rail in the control cabinet. ► Maximum cable length 1000 m. 1: screen 2: DIN rail 10.11: connection terminals sensor 1 to the VSE evaluation unit ►...