Graco Fire-Ball 300 Instructions And Parts List page 6

Drum or tank supply pumps
Hide thumbs Also See for Fire-Ball 300:

Advertisement

Supply Lines From Pumps To Dispensing Units
Distance
Annealed Steel Tube
Min. O.D.
< 25 ft. (7.6 m)
5/8 in.
> 25 ft. (7.6 m)
7/8 in.
> 75 ft. (23 m)
Contact your Graco distributor
A Incoming supply line
B 3/4 in. npt line strainer
C Hose or pipe to metered unit
D Position outlet down
C
D
Fig. 4
TO OUTLET
A
B
C
A 3 in. (76 mm), Supply line to wall
B 20 in. (510 mm), Main fluid shutoff valves
C 24 in. (610 mm), Main air line to floor
D 20 in. (510 mm), Between suction lines
Fig. 5
6
306520
Installation
Min. Tube Wall
Fittings
0.035 in.
Flareless
(0.89)
0.035 in.
Flareless
(0.89)
B
A
D
01497
Annealed Copper Tube
Min. O.D.
Min. Tube Wall Fittings Min. Size
5/8 in.
0.049 in.
type K
(1.24 mm)
7/8 in.
0.065 in.
type K
(1.65 mm)
1. Use a Y-type line strainer in oil supply lines. Locate
as close to the meter inlets as practical and where
they are easily accessible. Mount the strainer body
horizontally with the clean-out plug pointed down.
See Fig. 4. Periodically, relieve the pressure, and
remove and clean the metal strainers.
To order a 3/4 in. npt(f) line strainer, order Part No.
101078.
To order a 1/2 in. npt(f) line strainer, order Part No.
110877.
INJECTION HAZARD
To reduce the risk of serious injury
whenever you are instructed to relieve
pressure, always follow the Pressure
Relief Procedure on page 8.
2. See Fig. 5 for installation dimensions for the
supply line. Space the line ends to be adjacent to
the pump location. For annealed steel or copper
tubing lines, use a straight male coupling elbow
and a shutoff valve. For iron pipe, a shutoff valve
may be used instead. The shutoff valve must close
off 1/2 in. npt(f) openings for the Fire-Ball 300
pump, and it must close off 3/4 in. npt(f) openings
for the Fire–Ball 425 pump.
Air Lines
Air lines
Annealed Copper
O.D.
Type
L
Pump to
1/2 or
main air
3/8 in.
Compressor
1/2 in.
to main air
Standard Iron Pipe
Fittings
Flared
1/2 in.
Heavy
malleable iron
Flared
3/4 in.
Heavy
malleable iron
WARNING
Galvanized Pipe
Tube
Minimum
Nominal
Wall
Size
Thickness
0.035 in.
1/2 in. or 3/8 in.
(0.89 mm)
0.035 in.
1/2 in. or 3/8 in.
(0.89 mm)