7.2.4 Data format of Monitoring by Command(1H) and Setting by Command(2H)
Data
Measurement
Items
Current,
Voltage,
Active power,
Reactive power,
Apparent power,
Power factor,
Frequency,
etc.
Format①
<Multiplying factor>
<Example: Active power>
FFH⇒×10
00H⇒×1
FFH⇒×10
00H⇒×1
Note: For the active power (demand) and reactive power, ±1638.3MW(Mvar) becomes the
Note: For the power factor, "+" is showed lag, "-" is showed lead as with ME96's display.
7.15
Table
Multiplying
factor
Numerical value
High data
b31
b24 b23
Numerical value: 32-bit integer with a sign
Multiplying factor is fixed according to settings of primary current, primary voltage, and phase
wiring. (Refer to 7.2.5.)
Index number
Multiplying factor
02H
01H
00H
FFH
FEH
FDH
Multiplying
Numerical value
factor
-1
000000FFH⇒255
000000FFH⇒255
-1
FFFFFF01H⇒-255
FFFFFF01H⇒-255
upper(lower) value.
Data Format (1/8)
Data Format ①
b15
b8
b7
Index number
Low data
High data
b16 b15
-2147483648~2147483647
(80000000H~7FFFFFFFH)
2
×10
×10
×1
Actual value =
-1
Numerical value × Multiplying factor
×10
-2
×10
-3
×10
Actual value
-1
255×10
= 25.5[kW]
255×1 = 255[kW]
-1
-255×10
-255×1 = -255[kW]
(45/n)
b0
Low data
b7
b8
Remarks
= -25.5[kW]
LEN130391B