2. Set the language, time, date, network parameters, and system parameters on the Settings
Wizard screen.
3. After you perform the settings, the Bypass mode and No battery alarms are reported by the
MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
4. View the system running status diagram on the MDU to check that the UPS is working in bypass
mode.
5.3
Starting inverter
1. On the main menu, choose Common Functions and tap Inv. ON.
2. In the displayed login window, enter the user name and password, and tap
3. In the displayed dialog box, tap Yes to start the inverter.
System User
admin (system administrator)
operator (common user)
LCD Preset
WebUI Preset
Password
Password
000001
Changeme
000001
Changeme
11
.
To ensure system security,
change the LCD and
WebUI passwords after
the first login.