Testing; Ionisation Current - Riello RX80 S/PV Installation, Use And Maintenance Instructions

Premixed gas burners
Table of Contents

Advertisement

Available languages

Available languages

230V
~
50Hz
PE
L N
T6A
TS
L1
N
T1
T2
S3
XP7
X10
1
2
3
4
5
1
2
3
4
D9725
A1
– Electrical control box CM222
CN
– Connector
h1
– 1st stage hour counter
h2
– 2nd stage hour counter
MV
- Fan motor
SB
– Reset indicator
SO
– Ionization probe
TB
- Burner ground (earth) connection
TL
– Limit thermostat
TR
– 2nd stage thermostat
TA
– Ignition transformer
TS
– Safety thermostat
T6A – Fuse
V10
– V1
V11
– V2
X..
– Socket
XP.. – Socket
The cross section of the conductors must be at
least 1 mm2. (Unless requested otherwise by lo-
cal standards and legislation).
WARNING
TL
SB
h1
B4
A 1
X1
1
2
3
5
1
2
3
M
MV
Installation
h2
B5 T6 T7 T8
XP4
X4
X2
1
2
3
1
2
3
1
V10
5.8.1

Testing

Check that the burner goes off by opening the thermostats (TL);
check that the burner has locked out during operation by opening
the connector (CN) inserted in the probe's red wire, located out-
side the control box.
5.8.2

Ionisation current

The minimum current necessary for the control box operation is
5 µA. The burner gives a much higher current, meaning that
checking is not usually required.
Should you want to measure the ionization current anyway, you
must open the connector (CN1) inserted in the red wire and insert
a microammeter.
Control-box
D5006
11
GB
TR
C H IP C A R D
X5
4
1
2
3
4
2
TB
V11
Connector
TO BE DONE
BY INSTALLER
CARRIED OUT
IN THE FACTORY
Fig. 8
Probe
Fig. 9
20017376

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx100 s/pvRx120 s/pv200154862001583720015840

Table of Contents