NTP-G274 Replace the Air Filter of the ONS 15454 M2 Shelf
Assembly
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Note
The air filters are single-use only. They must not be cleaned and reused. This is a Telcordia NEBS requirement,
GR-63-CORE Issue 4.
Note
Air filters must be inspected every month. If they are dirty or clogged with dust, they must be replaced with
a new air filter.
Procedure
Step 1
Untighten the screw on the air-filter (see the following figure).
NTP-G40 Replace the Front Door , on page
This procedure replaces the air filter of the ONS 15454 M2 shelf assembly.
New air filter
NTP-G266 Install the ONS 15454 M2 Shelf
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, refer to the
Guide for Cisco CPT and Cisco ONS
As Needed
Remote
Provisioning or higher