Pilot Air PAC Series Users Maintenance And Spare Parts Manual page 28

Table of Contents

Advertisement

Input configuration: Sub-menu allowing you to configure the logic of all the control unit inputs and
Alarms and Warnings
-
All the alarms that occur are
visually displayed on the main
screen in the "Alarms and
warnings Panel", in the "Machine
Status Summary Panel" (see
Main Screen paragraph) and
acoustically via the buzzer.
-
The acoustic alarm can be
immediately silenced by pressing
the "RESET" key, while the alarm
indication on the LCD will only
disappear if the cause of the
alarm has been resolved.
-
The last 50 alarms are visible in
the "Alarms log" (see Main menu
paragraph) where you can check
their chronological order, the pressure and temperature in the instant in which they occurred.
The possible alarms are as follows:
Alarm! Minimum temp.:
Alarm! Maximum temp.:
28 |
P a g e
Start-Up and Operation
associate a function of your choice to input CN2-1, among: "oil filter, "air filter" and
"air pressure switch". By setting the configuration equal to 1, the input logic will be
denied. Vice versa, if left at 0 the logic will be normal.
Having reached the oil minimum temperature, the alarm BLOCKS the
compressor. To re-start the compressor, you need to wait for the temperature to
rise above the programmed value.
Having reached the oil maximum temperature, the alarm BLOCKS the
compressor. To re-start the compressor, you need to wait for the temperature to
go below the programmed value.
PLUS 56-75-Cod.197DD8805