Pilot Air PAC Series Users Maintenance And Spare Parts Manual page 26

Table of Contents

Advertisement

Inverter Menu
Enable Inverter
% Min functioning
Inverter Integral
Inverter Proportional : Defines the proportional part on the PID calculation of the inverter percentage.
Inverter Differential
Pressure at 100%
Minimum pressure % : The pressure at which the inverter must work at the % Min functioning percentage set.
Dryer Menu
Dryer ON
Minimum time
Temperature OFF
Temp. differential
Temperature offset
Functioning mode
Automatic
Continuous
Alarms Delay
Alarm type
Alarm
Warning
Extra run
26 |
P a g e
Start-Up and Operation
: Inverter enabling.
: Defines the frequency minimum percentage at which the inverter must work. The maximum
is 100%
: Defines the integral part on the PID calculation of the inverter percentage.
: Defines the differential part on the PID calculation of the inverter percentage.
: The pressure at which the inverter can work up to 100%
: Dryer Enabling.
: Defines the minimum maintenance time of the deactivated dryer. It serves to protect the
dryer compressor from over-frequent start-ups.
: Defines the value of the temperature at which the dryer compressor is deactivated.
: Defines the positive differential between the OFF temperature and the re-activation
temperature.
: Defines the difference between the temperature measured and the temperature displayed.
: Defines the functioning mode of the dryer:
: The compressor starts and stops based on the main motor of the compressor functioning.
: The dryer starts as soon as the compressor is switched on and will only stop when it is
switched off.
: Defines the delay with which the dryer alarms are displayed.
: Defines the effects of the alarm on the compressor:
: Blocks the compressor.
: Warning without blocking the compressor.
: Defines the time in which the dryer must continue to work, also after the compressor motor
has stopped, if the functioning mode is set to automatic.