6-13. Control of R-sensor OFF Point
- J1, J2 On Main PCB
A. LOW COOLING OPTION
(1) Adjust R-Sensor off point (Max 3.0deg down)
(2) the following actions are recommended for service.
① Resistance (R52) : Default resistance (31.4Kohms)
② Resistance (R53) : Cut the "J1" off to reduce basic resistance by 1.5 ° C. (2KΩ up)
③ Resistance (R54) : Cut the "J2" off additionally to reduce basic resistance by 1.5°C. (total 4KΩ up)
ex) R52 = R-SENSOR OFF point
R52 + R53 = R-SENSOR OFF point - 1.5°C
R52 + R53 + R54 = R-SENSOR OFF point - 3 ° C
Input
NEO-V SVC MANUAL
Output
- Control Resistance of R sensor OFF Point
37