6-5. Comp Control
- R-Sensor
- Short Circuit / Defrost Mode
- Elapsed time after comp off
A. General Control
1) if Defrost Mode
Precool
Heater On
Pause
Fan Delay
* compressor details operation sees chapter "Defrost Control".
2) if Normal Mode
① R-Sensor Error
- Compressor is controlled of the time by RT-Sensor's range.
② No R-Sensor Error
- Compressor is controlled of the setting On/Off point (reference 'Refrigerator Control')
- R-Sensor <= Comp Off point
- R-Sensor > Comp On point
B. Prevention of Compressor Restart
- Compressor doesn't work within 6 minutes after Compressor turns off. (This is to protect comp)
ex) Compressor doesn't work after COMP turns off even though R-sensor is on condition
Input
Comp On
Comp Off
Comp Off
Comp On
->
Comp Off
->
Comp On
NEO-V SVC MANUAL
Output
- Comp On/Off Operation
25