6-6. Defrost Control
C. Low Temp. Defrost Mode
CONTENTS
When RT Mode is Low-A,B,
"Low Temp. defrost mode" starts immediately as long as total time (COMP on + off time) is 24 hrs.
Inrush conditions
◆ Mode Maintain conditions
ⅰ. RT Mode must maintain Low-A,B
Each stage
Release conditions
When RT Mode isn't low A, B, "Low Temp. defrost mode" is turned off immediately.
Mode release
At Low Temp. Defrost Mode, normal defrost mode is performed by satisfying the normal conditions.
D. High Temp. Defrost Mode
CONTENTS
When RT Mode is High-A,B,
Defrost mode starts immediately when total operation time of COMP is 24hrs.
◆ Mode Maintain conditions
Inrush conditions
ⅰ. RT Mode must maintain High-A,B
ⅱ. The door maintains closing.
ⅲ. No happened the Error
Each stage
Release conditions
When the condition doesn't maintain, "High Temp. defrost mode" is turned off immediately.
Mode release
If "High Temp. defrost mode" is released, normal defrost mode is performed.
① R-Sensor < Comp Off Point - 3.0℃
PreCool
② after 25 minutes
case 1) D-Sensor Error
- after 30 minutes
case 2) RT-Mode is "Normal-A" & No open the door
Heater On
- D-Sensor > 8℃
case 3) Else
① D-Sensor > 10℃
② after 85 minutes
Pause
- after 10 minutes
Fan Delay
- after 1 minute
① R-Sensor < Comp Off Point - 3.0℃
PreCool
② after 25 minutes
① D-Sensor > 10℃
Heater On
② after 60 minutes
Pause
- after 10 minutes
Fan Delay
- after 1 minute
NEO-V SVC MANUAL
EXPLANATION
EXPLANATION
28