6-11. Function Switch Control (Main PCB Location)
- Test Switch
- Time Switch
A. Test Switch
- Using Test Switch (Part No. SW2) in the Main PCB, short-circuit mode, the Power Saving mode,
As forced defrost mode can be entered.
default
Short Circuit : Off
Power Saving : Off
As forced defrost : Off
* Pushing the Test Switch for 4 times, Test Mode is become default state.
B. Time Switch
- Using Test Switch (Part No. SW1) in the Main PCB, it can send forcedly the time.
① Short Click the Time Switch (within 1 second)
- 1 min : Click Time Switch one time on MAIN PCB.
② Push the Time Switch (more than 1 second)
- 30 min : If you press FAST KEY continuously, you can reduce 30 minutes on each 2.5 seconds with buzzer.
Input
Test Switch 1 time
Short Circuit : On
->
Power Saving : Off
As forced defrost : Off
NEO-V SVC MANUAL
Output
- Short Circuit / Power Saving / As Forced Defrost Mode
selection.
- Time Pass control
Test Switch 2 times
Short Circuit : Off
->
Power Saving : On
As forced defrost : Off
33
Test Switch 3 times
Short Circuit : Off
->
Power Saving : Off
As forced defrost : On