8.6.

Random Auto Restart Control

• If there is a power failure during air conditioner operation, operation will be automatically restarted after 3 to 4 minutes when the
power is resumed.
It will start with previous operation mode and airflow direction.
• Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
• Auto Restart Control is not available when Timer is set.
• This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)
8.7.

Airflow Direction Control

Vertical Airflow Direction Auto-Control
• When set a Airflow Direction Auto-Control with remote
control, the louver swings up and down as shown in the
diagram.
• The louver does not swing when the Indoor Fan Motor
stops during operation at the upper limit.
• When stopped with remote control, the discharge vent is
reset, and stopped at the closing position.
• During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0° - 36° to 12° - 28° under
Cooling and Soft Dry operation mode.
1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation.
2. In Heating operation, when the piping air temperature reaches 38°C, the louver is changed from upper to lower limit position. When the
piping air temperature falls to 35°C, the louver is changed from lower to upper limit position.
Vertical Airflow Direction manual Control
• When the manual Airflow Direction Selection Button is
pressed, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in
the diagram.
The louver can be adjusted by pressing the button to the
desired louver position.
• When the remote control is used to stop the operation, the
discharge vent is reset, and stopped at the closing position.
• During Anti-dew condensation prevention, Airflow Direction
Manual control angle change from 14°, 19°, 24°, 30°, 36° to
16°, 18°, 20°, 22°, 24° under Cooling and Soft Dry operation
mode.