8.6 Departure from reference setting
The class index plus an error not exceeding the class index.
8.7 Departure from reference frequency
Over the range of 47 – 52 Hz (50Hz nominal) or 57 – 62 Hz (60Hz nominal), the variations in accuracy are the
class index plus an error not exceeding the class index.
8.8 Departure from reference temperature
The variations in accuracy over the operating temperature range is the class index plus an error not exceeding the
class index.
8.9 High Set Overcurrent Function
Operating Current
≤ ±5% of setting
Reset current
>95% of operating current
Overcurrent Time (OCT)
≤ ±1% or ±10ms (whichever is greater)
8.10 Forward and Reverse Directional Earth Fault Functions
Operating Current
≤ ±5% of setting
Reset Current
>95% of operating current
Definite Time Lag
≤ ±1%
DEF DTL Timers (DEFF, DEFR)
≤ ±1% or ±5ms (whichever is greater)
8.11 Power Swing (PS) Impedance Variation Setting Range
Characteristic or Impedance Variation
≤ ±5% error
8.12 Timing
Figures 1, 2 and 3 shown typical timing curves.
8.13 Fault locator
Accuracy is dependant upon circuit configuration and power flow conditions.
8.14 Thermal Withstand
Continuous and Limited Period Overload
AC Current Inputs
12A
15A
30A
AC Voltage Input –3.5Vn
Short Term Overload
340A
©2011 Siemens Protection Devices Limited
7SG164 Ohmega 400 Series Performance Specification
Continuous
for 10 minutes
for 2 minutes
Continuous
for 1 sec
Chapter 5 Page 8 of 13