Z3 PF Shape Factor 2
Z3 PF Time Delay
Z3 Earth Fault
Z3 EF Type
Z3 EF Impedance (Fwd)
Z3 EF Impedance (Rev)
Z3 EF Time Delay
Direct Zone 4 Trip
Z4 Phase Fault
Z4 PF Impedance
Z4 PF Time Delay
Z4 Earth Fault
Z4 EF Impedance
Z4 EF Time Delay
Power Swing Menu
Setting
Power Swing Detector
PSD Zone blocking
PSD Shape
PSD Blinders
PSD Inner Fwd Impedance
PSD Inner Rev Impedance
PSD Inner Fwd Blinder
PSD Inner Rev Blinder
PSD Outer Multiplier
PSD Transit Time
Auxiliary Protection Menu
Setting
High Set
HS Level
HS Time Delay
Stub Protection
SP Level
SP Delay
SOTF
SOTF Mode
SOTF O/C Operate Level
VT Supervision
VTS Latched Operation
VTS Mode
VTS Phase Fault Inhibit
VTS Input Source
VTS Ires Level
VTS Vop Level
VTS 3PV Level
VTS 3PLOV Delay
©2013 Siemens Protection Devices Limited
0, 0.01, ... 1.00
0, 10, ... 10000ms
Enabled, Disabled
Fwd Mho, Rev Mho, Offset Mho
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 10, ... 10000ms
ENABLE, DISABLE
Enabled, Disabled
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 10, ... 10000ms
Enabled, Disabled
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 10, ... 10000ms
Range
ENABLE, DISABLE
Zone 1 | Zone 2 | Zone 3 | Zone 4
CIRCULAR, RECTANGULAR
ENABLE, DISABLE
0.1, 0.2, ... 250.0
0.1, 0.2, ... 250.0
0.1, 0.2, ... 250.0
0.1, 0.2, ... 250.0
1.05, 1.06, ... 2.00
0, 5, ... 1000ms
Range
(Disabled..Enabled)
(0.1..35)
(0..1000)
(DISABLE..ENABLE)
(0.1..2)
(0..1000)
(Disabled..Enabled)
(AC SOTF..DC SOTF)
(0.3..4)
(Disabled..Enabled)
(Disabled..Enabled)
(Alarm Only..Alarm & Inhibit)
(Disabled..Enabled)
(Res I/V...NPS I/V)
(0.05..2)
(1..100)
(1..70)
(0..10)
7SG1641 Ohmega 402 60 Relay Settings
1.00
2000ms
Enabled
Offset Mho
24.00 Ohm
8.00 Ohm
2000ms
DISABLE
Enabled
8.00 Ohm
0ms
Enabled
8.00 Ohm
0ms
Default
ENABLE
Zone2-4
CIRCULAR
DISABLE
24.0 Ohm
8.0 Ohm
16.0 Ohm
16.0 Ohm
1.50x
50ms
Default
Enabled
4 x In
0ms
ENABLED
1 xIn
0ms
Enabled
AC SOTF
0.3 x In
Enabled
Enabled
Alarm & Inhibit
Enabled
Res I/V
0.3 x In
20v
20v
1s