Siemens 7SG164 Ohmega 400 Series Manual page 51

Table of Contents

Advertisement

1 Menu Settings
System Configuration Menu
Setting
Active Group
CVT in use
CT Ratio
VT Ratio
Alternate Setting Group
View/Edit Group
Default Screens Timer
Date
Time
Backlight timer
Change Password
Relay Identifier
Distance Protection Menu
Setting
Active Scheme
CT Secondary
Line Angle
EF Comp Z0/Z1 ratio
EF Comp Z0 angle
POR Weak Infeed
WI Local Trip
WI Voltage Level
Z1 Phase Fault
Z1 PF Impedance
Z1 PF Time Delay
Z1 Earth Fault
Z1 EF Impedance
Z1 EF Time Delay
Z2 Phase Fault
Z2 PF Impedance
Z2 PF Time Delay
Z2 Earth Fault
Z2 EF Impedance
Z2 EF Time Delay
Z3 Phase Fault
Z3 PF Type
Z3 PF Impedance (Fwd)
Z3 PF Impedance (Rev)
Z3 PF Shape Factor 1
©2013 Siemens Protection Devices Limited
Range
1, 2 ... 8
YES, NO
0, 100, ... 5000: 1,2,5
1000, 1100, ... 10000, 11000, ... 600000:
90, 95, ... 130
1, 2 ... 8
1, 2 ... 8
Off..60
Off..60
AAAA ... ZZZZ
Up to 16 characters
Range
Time Stepped, PUR, POR1, POR2, BOR
1, 2, 5
0, 5, ... 90 Deg
0, 0.01, ... 10.00
0, 5, ... 355 Deg
Enabled, Disabled
Enabled, Disabled
5, 5.5, ...85 v
Enabled, Disabled
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 10, ... 10000ms
Enabled, Disabled
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 10, ... 10000ms
Enabled, Disabled
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 10, ... 10000ms
Enabled, Disabled
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 10, ... 10000ms
Enabled, Disabled
Fwd Mho, Rev Mho, Offset Mho, Offset
Shaped
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0.5, 0.51, ... 10.0,
10.1, 10.2, ... 100,
101, ... 250
0, 0.01, ... 1.00
7SG1641 Ohmega 402 60 Relay Settings
Default
1
NO
2000:1
132000:110
1
1
60
1/ 1/1980
00:00:00
5
NOT ACTIVE
OHMEGA 402-60
Default
Time Stepped
1A
75 Deg
2.50
75 Deg
Enabled
Enabled
54.0 v
Enabled
8.00 Ohm
0ms
Enabled
8.00 Ohm
0ms
Enabled
16.00 Ohm
1000ms
Enabled
16.00 Ohm
1000ms
Enabled
Offset Mho
24.00 Ohm
8.00 Ohm
1.00