Replacement battery
cartridge (internal UPS
battery replacement)
Battery Access
Battery replacement
description
VOLTAGE REGULATION
Voltage regulation
description
Overvoltage correction
Undervoltage correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression joule
rating
UPS AC suppression
response time
EMI / RFI AC noise
suppression
PHYSICAL
Installation form factors
supported with included
accessories
Installation form factors
supported with optional
accessories
Primary form factor
UPS / Power Module
dimensions in primary form
factor (height x width x
depth / inches)
UPS / Power Module
dimensions in primary form
factor (height x width x
depth / cm)
Installed whole system
total rack space height
(rack spaces)
Secondary form factor
Installed whole system
dimensions in secondary
form factor (height x width
x depth / inches)
RBC94-3U
(quantity 3)
Front panel battery access door
Hot-swappable, user replaceable batteries
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 167 to 260
Input voltages between 228V and 260V are reduced by 12%
Input voltages between 167V and 194V are boosted by 12%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure, overload and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation
1020
Instantaneous
Yes
4 post 19 inch rackmount (mounting rail kit included)
2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND)
Rackmount
5.2 x 17.5 x 25
13.3 x 44.4 x 63.5
3U
Tower (requires 2-9USTAND)
17.5 x 5.2 x 25