Specifications
OUTPUT
Output Volt Amp Capacity
(VA)
Output kVA capacity (kVA)
Output Watt Capacity
(watts)
Output kW capacity
Output power factor
Nominal Output Voltage(s)
Supported
Nominal Voltage details
Frequency compatibility
Output voltage regulation
(line mode)
Output voltage regulation
(Battery mode)
Built-in UPS output
receptacles
Output receptacle details
Output circuit breaker
Output AC waveform (AC
mode)
Output AC waveform
(battery mode)
INPUT
Rated input current (at
maximum load)
Nominal Input Voltage(s)
Supported
UPS input connection type
UPS Input cord length (ft.)
UPS Input cord length (m)
Recommended Electrical
Service
BATTERY
Full load runtime (minutes)
Half load runtime (minutes)
DC system voltage (VDC)
Battery recharge rate
(included batteries)
5000
5
3750
3.8
0.8
120V; 208V
120V output is limited to 600VA / 450 watts (maximum)
60 Hz
208 & 120V (-6%, +20%)
+/- 5%
2 5-15R outlet(s); 2 L6-20R outlet(s); 1 L6-30R outlet(s)
120V 5-15R outlets are limited to 600VA / 450 watts (maximum)
20A double pole breaker supports L6-20R outlets, 5A breaker supports 5-15R outlets, L6-30R outlet is
unbreakered
Sine wave
Pure Sine wave
24A
208V AC
L6-30P
10
3
30A 208V
8.5 min. (3750w)
20 min. (1875w)
48
Less than 4 hours from 10% to 90%