Connecting 120 Vac Power - Pro-Tec Welding PRO-TEC 215 MP Operating Manual

Table of Contents

Advertisement

4.6 Connecting 120 VAC Power

Installation must meet all National and Local
Codes. This installation must be
nected
by a Suitably Trained and Qualified
Tradesperson.
DO NOT TOUCH any live electrical parts or conductors.
 Touching live electrical parts can cause fatal
shocks or severe burns. The electrode and
work circuit is electrically live whenever the
output is on.
 DO NOT WORK ALONE! The Input Power
Supply circuit and Power Source internal cir-
cuits are also live when power is on.
NOTE 4: These Products configures the Power Source
to the operating parameters for 120 / 208 / 230 / 240
VAC.
Electrical Input Requirements
Operate the Power Source from a single-phase, 50/60
Hz, AC Power Supply
available on
Supply Voltage
must match one of the electrical input
voltages shown in this manual.
Power Adapter
Use the
(2 and 3) to connect the Power Source Input Power Cord Plug (1) to the Receptacle Outlet (4).
1 Power Source
Input Power
Cord plug (Nema
6-50P)
2 Power adapter
receptacle
(Nema 6-50R)
3 Power adapter
plug (Nema 5-
15P)
4 Customer Sup-
plied Receptacle
Outlet (Nema
5−20R or Nema
5-15R)
© 2018 Global Welding LLC
Refer to Figure 1 and
mum Input Supply Voltage and Fuse Size.
120 Volts AC Input Supply
electrically con-
Individual Branch Circuit
120VAC / 15 A Outlet
120VAC / 20 A Outlet
Table 1 – 120VAC Electrical Fuse
NOTE 5: The time-delay fuse or circuit breaker of an
individual branch circuit may have nuisance tripping
when welding with this Power Source due to the am-
perage rating of the time-delay fuse or circuit breaker.
The recommended time delay fuse or circuit breaker
size
for welding is shown in
Voltage = 120 VAC)
recommended for this application. Fuse/Circuit Breaker
size is based on not more than 200% of the rated input
amperage of the Power Source. Refer to National Elec-
trical Code Article 630.12.
SITE. The
Input
Figure 1 – 120 VAC Electrical Input Power Supply Connections
Page
19
Table 1
for connection, maxi-
Delay Fuse or Circuit Breaker
Voltage with
or Circuit Breaker
Table 1
and an individual branch circuit is
Operating Manual No: PWOM-215/250MP-001
INSTALLATION
Size
30 Amps
40 Amps
Size
(with Input Supply