CONNECTION TO POWER MAINS

THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
The air-handling unit is rated for connection to single-phase AC 230 V/50 (60) Hz power mains. The unit must be connected to power
mains using durable, insulated and heat-resistant conductors (cables and wires) with minimum cross section not less than 1 mm
The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the
event of overload or short-circuit. The position of the external automatic circuit breaker must ensure free access for quick power-off of
the unit. The circuit breaker trip current must correspond to the unit current consumption, refer to the Technical data section.
Connect the cables to the control unit using the cable glands on the side of the unit.
Make the electric connections through the terminal block, located in the control unit, in compliance with the External wiring diagram.
230 V/ 50(60) Hz
Designation
NO
SМ1*
SМ2 *
РК*
* Is not included in the delivery set.
** Maximum connecting cable length is 20 m!
www.ventilation-system.com
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED
DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE PROXIMITY
AND PARALLEL TO THE CONTROL PANEL CABLE! DO NOT COIL THE
CONTROL PANEL CABLE WHILE LAYING ITS OUT.
External control units wiring diagram for units with an A14 control panel
PK re alarm panel
(remove the jumper while
connecting the contact)
QF
XP
L
N
PE
1
2
3
4
5
Name
External control unit contacts
Supply air damper actuator
Exhaust air damper actuator
Contact from fire alarm panel
MANUFACTURER'S LABEL.
AND WILL VOID THE WARRANTY.
Access to the control unit
Humidity
sensor
External device
NO (CO
sensor)
3
+U
2
GND
2
0-10V
1
РК
+U 0-10V
GND
C
GND Tx
6
7
8
9
10
11
12
LF230
LF230
LF230
NO
Electric actuators
Control panel
of the external air dampers
- Tx Rx +
SM1
SM2
supply
exhaust
L1 N
L1 N
Rx
+U
SM-L
SM-N
13
14
15
16
17
Model
Wire**
2 x 0.75 mm
2 x 0.75 mm
2 x 0.75 mm
2 x 0.75 mm
.
2
X1
2
2
2
2
13