USER'S MANUAL
ROOF FANS
VENTS VKV \ VKH \ VKV EC \ VKH EC \ VKMK \ VKMKp \ VOK \ VOK1 SERIES

Advertisement

Table of Contents
loading

Summary of Contents for Vents VKV Series

  • Page 1 USER'S MANUAL ROOF FANS VENTS VKV \ VKH \ VKV EC \ VKH EC \ VKMK \ VKMKp \ VOK \ VOK1 SERIES...
  • Page 2: Table Of Contents

    CONTENTS Purpose ........................... Delivery set..........................Designation key ........................Technical data ........................Safety requirements ......................Installation and set-up ...................... Connection to power mains ................... Storage regulations......................Technical maintenance ..................... Manufacturer's warranty ....................Certificate of acceptance ....................Warranty card ........................
  • Page 3: Purpose

    PURPOSE The VENTS VKV, VKH, VKV EC, VKH EC, VKMK, VKMKp, VOK, VOK1 fans in metal casing with inlet diameter from 220 to 500 mm and from 250 mm to 560 mm for VKV EC and VKH EC models, hereinafter referred to as fans, are designed for ventilation of various industrial premises, pools, apartment buildings, offices, hospitals, restaurants, and other premises heated in winter time.
  • Page 4: Designation Key

    DESIGNATION KEY Designation key of the VKV, VKH, VOK fans XXX X X XXX Impeller diameter [mm]: 200; 220; 225; 250; 280; 300; 310; 350; 355; 400; 450; 500 E – single-phase D – three-phase Number of motor poles: 2, 4, 6. Fan designation: VKV –...
  • Page 5 Designation key of the VKMK, VKMKp, VOK1 fans XXX XXX Impeller diameter [mm]: 150; 200; 250; 315 Fan designation: VKMK – centrifugal roof fan with a round cover VKMKp – centrifugal roof fan with a round cover and a base plate VOK1 –...
  • Page 6: Technical Data

    TECHNICAL DATA Fan overall dimensions: Dimensions [mm] Model Weight [kg] VKH 2E 220 VKH 2E 225 VKH 2E 250 10.1 VKH 2E 280 10.2 VKH 4E 310 10.2 VKH 4D 310 10.2 VKH 4E 355 15.6 VKH 4D 355 15.6 VKH 4E 400 21.0 VKH 4E 450...
  • Page 7 Technical data: VKV / VKH VKV / VKH VKV / VKH VKV / VKH 2E 220 2E 225 2E 250 2E 280 Voltage [V] 1~ 220-240 1~ 220-240 1~ 220-240 1~ 220-240 Frequency [Hz] Power [W] Current [A] 0.38 0.44 0.65 1.15 1.51...
  • Page 8 VKH ЕС VKV ЕС Fan overall dimensions: Dimensions [mm] Model Weight [kg] VKH 250 ЕС VKH 280 ЕС VKH 310 ЕС VKH 355 ЕС VKH 400 ЕС VKH 450 ЕС VKH 500 ЕС VKH 560 ЕС Dimensions [mm] Model Weight [kg] VKV 250 ЕС...
  • Page 9 Technical data: VKV / VKH VKV / VKH 250 ЕС 280 ЕС Unit voltage [V/50 (60) Hz] 1~ 200-277 1~ 200-277 Power [kW] 0.485 0.455 Current [A] Maximum air flow [m3/h] 1750 2650 RPM [min 3580 2600 Sound pressure level at a distance of 3 m [dBA] Max.
  • Page 10 VKMK VKMKp Fan overall dimensions: Dimensions [mm] Model Weight [kg] VKMK 150 VKMK 160 VKMK 200 VKMK 250 10.1 VKMK 315 12.3 VKMKp 150 VKMKp 160 VKMKp 200 VKMKp 250 VKMKp 315 11.6 Technical data: VKMK 150 VKMK 200 VKMK 250 VKMK 315 VKMK 160 Voltage [V]...
  • Page 11 Fan overall dimensions: Dimensions [mm] Model Weight [kg] VOK 2E 200 VOK 2E 250 VOK 4E 250 VOK 2E 300 10.5 VOK 4E 300 10.5 VOK 4E 350 12.0 Technical data: VOK 2E 200* VOK 2E 250* VOK 4E 250* VOK 2E 300 VOK 4E 300* VOK 4E 350...
  • Page 12 VOK1 Fan overall dimensions: Dimensions [mm] Model Weight [kg] VOK1 200 VOK1 250 VOK1 315 11.5 Technical data: VOK1 200 VOK1 250 VOK1 315 Voltage [V] 1~ 230 Frequency [Hz] Power [W] Current [A] 0.28 0.21 0.48 0.51 0.75 Maximum air flow [m3/h] 1070 1050 1700...
  • Page 13: Safety Requirements

    SAFETY REQUIREMENTS DISCONNECT THE UNIT FROM POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL READING OF THE PRESENT USER'S MANUAL.
  • Page 14: Installation And Set-Up

    INSTALLATION AND OPERATION GUIDELINES The fan is designed for mounting on a roof directly above a ventilation shaft or an air duct. Installation procedure and mounting sequence are shown on pages 15-18. To prevent water and snow ingress inside a ventilation shaft, the fan can be mounted on a roof curb.
  • Page 15 VKV, VKV ЕС...
  • Page 16 VKH ЕС...
  • Page 17 VKMK VKMKp...
  • Page 18: Connection To Power Mains

    VOK, VOK1 CONNECTION TO POWER MAINS DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS. THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER'S LABEL.
  • Page 19 The recommended automatic circuit breaker rated current and the cable cross section for various fan models are stated in the table on page 19. The above cross sections are for reference only. The actual cross section depends on maxi- mum permissible wire heating, its material, insulation, length and installation method (i.e. overhead, in pipes or inside the walls).
  • Page 20 ~230 V РЕ 50 (60) Hz “ON” “OFF” ~400 V 50 (60) Hz “ON” “OFF”...
  • Page 21 Wiring diagram of the VKV/VKH 2E 220, VKV/VKH 2E 225, VKV/VKH 2E 250, VKV/VKH 2E 280, VKV/VKH 4E 310 and VKV/VKH 4E 355 fans ~230 V РЕ 50 (60) Hz where QF is the automatic circuit breaker (not included in the delivery set) X1 is the terminal block Wiring diagram of the VKV/VKH 4E 400, VKV/VKH 4E 450 and VKV/VKH 6E 500 fans...
  • Page 22 Wiring diagram of the VKV/VKH 4D 310 fan ~400 V 50 (60) Hz РЕ where QF is the automatic circuit breaker (not included in the delivery set) X1 is the terminal block Wiring diagram of the VKV/VKH 4E 355, VKV/VKH 4D 400 and VKV/VKH 4D 450 fans ~400 V 50 (60) Hz РЕ...
  • Page 23 Wiring diagram of the VKV/VKH 250 EC, VKV/VKH 280 EC and VKV/VKH 310 EC fans Cable 1 Cable 2 Contact Connection Colour Function Black Mains 50/60 Hz, phase Blue Mains 50/60 Hz, zero wire Green/Yellow Protective ground conductor White 1 Fault relay, normally closed contact White 2 Fault relay, COMMON...
  • Page 24 Wiring diagram of the VKV/VKH 500 EC fan Terminal Connection Function Protective ground conductor Mains; L3 Mains; L2 Mains; L1 Signal-actuated relay, voltage-free signalling contact; error-triggered break contact Status relay; dry signal contact for status message service; change-over contact, shared connection; maximum contact closing current 250 VAC/max.
  • Page 25 Wiring diagram of the VKMK/VKMKp 150; VKMK/VKMKp 200; VKMK/VKMKp 250 and VKMK/VKMKp 315 fans ~230 V РЕ 50 (60) Hz where QF is the automatic circuit breaker (not included in the delivery set) X1 is the terminal block Wiring diagram of the VOK 2E 200; VOK 2E 250; VOK 4E 250; VOK 2E 300; VOK 4E 300;...
  • Page 27 VKH ЕС...
  • Page 28 VKV, VKV ЕС...
  • Page 29 VKMK, VKMKP...
  • Page 30: Storage Regulations

    VKV, VKV ЕС STORAGE REGULATIONS Store the unit in the manufacturer's original packaging box in a dry closed ventilated prem- ise with temperature range from +5 °C to + 40 °C and relative humidity of up to 80 % (at +20 °C).
  • Page 31: Technical Maintenance

    TECHNICAL MAINTENANCE Fan maintenance means periodic cleaning of the surfaces from dust and dirt. Switch the fan off while doing any maintenance operations! Use a dry soft brush or compressed air to remove dust. The impeller blades require thorough cleaning at least once in 6 months. To clean the soiled fan internal parts perform a partial fan dismantling.
  • Page 32 VKH ЕС VKV, VKV ЕС...
  • Page 33 VKMK, VKMKP VOK, VOK1...
  • Page 34: Manufacturer's Warranty

    MANUFACTURING WARRANTY While buying the present product the Customer agrees to accept the following warranty conditions: The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user's observance of the transportation, storage, installation, and operation regulations.
  • Page 35: Certificate Of Acceptance

    2014/35/EU and CE-marking Directive 93/68/EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility. This certificate is issued following the test on the samples of the product referred to above. Model „VENTS “ VKV ЕС VKH ЕС VKMK...
  • Page 36 V12EN-09...