Setting The Transmission Rate; Setting The Station Address; Download Modified Project To The Pnozmulti Safety System - Pilz PNOZ mc4p Operating Manual

Configurable safety systems pnozmulti
Hide thumbs Also See for PNOZ mc4p:
Table of Contents

Advertisement

Commissioning
6.4

Setting the transmission rate

Set the transmission rate using DIP switches S1 and S2 (DR).
Transmission rate
125 kBit/s
250 kBit/s
500 kBit/s
---
6.5

Setting the station address

The station address of the expansion module PNOZ mc4p is set from 0 ... 63 (binary) using
DIP switches 1 to 32.
Station address
0
1
2
3
...
62
63
6.6

Download modified project to the PNOZmulti safety system

As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat-
ing instructions for the base unit.
Operating Manual PNOZ mc4p
21054-EN-05
DIP switch
S1
Off
On
Off
On
INFORMATION
The transmission rate cannot be changed during operation.
DIP switch
32
16
Off
Off
Off
Off
Off
Off
Off
Off
...
...
On
On
On
On
NOTICE
For the commissioning and after every program change, you must check
whether the safety devices are functioning correctly.
S2
Off
Off
On
On
8
4
2
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
On
...
...
...
On
On
On
On
On
On
1
Off
On
Off
On
...
Off
On
16