Page 1
PNOZ m EF PDP Link Configurable, safe small controllers PNOZmulti 2 Operating Manual-1003019-EN-04...
Page 2
Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
Download modified project to the PNOZmulti safety system Series connection of 4 decentralised modules Voltage drop 6.5.1 Guidelines for various cable types 6.5.2 Calculation example Section 7 Operation Messages Fault detection Section 8 Technical details Safety characteristic data Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
Page 4
Contents Section 9 Order reference Product Accessories Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ m EF PDP Link. It is valid until new docu- mentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
Page 6
Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
The product has the following features: Can be configured in the PNOZmulti Configurator Max. 4 PNOZ m EF PDP Link can be connected to the base unit Max. 4 decentralised modules can be connected to the link module PNOZ m EF PDP...
E-STOP equipment Safety circuits in accordance with VDE 0113 Part 1 and EN 60204-1 The product PNOZ m EF PDP Link meets the requirements of the standards EN 81-20, EN 81-22 and EN 81-50, harmonised under the Lifts Directive 2014/33/EU, and the re- quirements of the standard EN 115-1, harmonised under the Machinery Directive 2006/42/EC.
Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
The safety device remains effective in the case of a component failure. Functions The link module PNOZ m EF PDP Link is used to safely transfer the input information from decentralised modules to the control system PNOZmulti 2. The function of the inputs and outputs on the control system depends on the safety circuit created using the PNOZmulti Configurator.
Damage due to electrostatic discharge! Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm 22,5 (0.88") Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
Shielded cables must be used from a cable length of 30 m or in environments with strong interferences. Pilz pre-assembled cable can be used to connect the decentralised modules (see order reference). The plug-in connection terminals are either designed as cage clamp terminals or screw terminals (see order reference).
PDP67 F 8DI ION white blue black grey Connection when using the PSS SB BUSCABLE LC in conjunction with a Pilz self-assembly "PSS67 M12 connector" (see order reference in the Technical Catalogue) PNOZ m EF PDP Link PDP67 F 8DI ION brown...
Voltage drop per 10 m and per 100 mA PSS SB BUSCABLE LC 0.1 V Sensor cable 0.25 mm 0.15 V Sensor cable 0.34 mm 0.11 V Sensor cable 0.5 mm 0.07 V Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
I0: Module's consumption. I1 ... I5: Load current taken from the module U1 … U4: Voltage drop on the respective connection path Total voltage drop from the link module PNOZ m EF PDP Link to the final PDP67 F 8DI ION: total = 1.3 V + 0.825 V + 0.5 V + 0.10 V = 2.725 V...
The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base unit. The PNOZmulti safety system is ready for operation when the "POWER" and "RUN" LEDs on the base unit and the "READY" LED on the PNOZ m EF PDP Link are lit continuously. Messages Legend...
Temperature range -25 - 70 °C Climatic suitability In accordance with the standard EN 60068-2-30, EN 60068-2-78 Condensation during operation Not permitted Max. operating height above sea level 2000 m EN 61131-2 Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
Page 21
Conductor cross section with spring-loaded terminals: Flexible with/without crimp connector 0,2 - 2,5 mm², 24 - 12 AWG Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals 9 mm Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function's SIL/PL values. Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
M12sm 30 m PSS67 Cable M8af Cable, straight M12 connector, angled M8 socket, 4-pin, 380 204 M12sm PSS67 Cable M8af Cable, straight M12 connector, angled M8 socket, 4-pin, 5 380 205 M12sm Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
Page 24
Adapter for connection to safety switch PSENmag 380 300 PSEN cs adapter Adapter for connection to safety switch PSENcode 380 301 PSEN sl adapter Adapter for connection to safety switch PSENslock 380 325 Operating Manual PNOZ m EF PDP Link 1003019-EN-04...
Page 26
Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...