1
Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device or load. In
so doing, take all the circuit breakers into account, which support dangerous voltages to the
device and or load.
These instructions are an integral part of the product, and must remain with the end customer.
2
Intended use
Switching and brightness setting for luminaires with DALI interface
Setting the colour temperature for luminaires with DALI Device Type 8 for Tunable White
in accordance with IEC 62386-209
Mounting in appliance box according to DIN 49073
Operation with suitable cover
Since error-free interaction cannot be guaranteed in combination with other DALI controls,
it is thus not recommend.
Product characteristics
DALI supply for a maximum of 18 DALI subscribers
Parallel switching of up to 4 DALI control units with the option of supplying up to 72 DALI
subscribers
Storing of minimum brightness, coldest and warmest colour temperature
Switching on with the last set brightness/colour temperature or saved brightness/colour
temperature
With 2-channel button cover: Adjustment of the colour temperature via right rocker
3
Operation
These instructions describe operation with a 1-channel button cover. Operation with different
covers is described in the instructions for the cover in question. Operation using 2-wire or 3-wire
extension essentially corresponds to operation on the main device.
With a 2-channel button cover, the left rocker works like the 1-channel button cover. The
right rocker is used to directly set the colour temperature.
Switching the light
Brief press on the button cover: Light is switched on or off at the last set brightness/colour
temperature or a saved brightness/colour temperature.
Long press on the button cover at the bottom: Light is switched on at minimum brightness.
Adjusting the brightness
Long press the button cover at the top or bottom.
Setting the colour temperature
Press the button cover in the switched-on state at the top, bottom or over the entire sur-
face twice within 0.4 seconds (double-click). The light switches off and on again.
Long press the button cover at the top or bottom.
82598922
19.03.2020
1 / 6

Advertisement

loading

Summary of Contents for Gira System 3000

  • Page 1 System 3000 Flush-mounted DALI Power control unit insert Flush-mounted DALI Power control unit insert Order no.: 5406 00 Operating instructions Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, fire or property damage possible. Please read and follow manual fully.
  • Page 2 System 3000 Flush-mounted DALI Power control unit insert After a further double click, the insert switches back to normal operation and signals this with a short switching off and on again. After one minute without operation, the insert also returns to normal operation.
  • Page 3 System 3000 Flush-mounted DALI Power control unit insert Connecting and fitting the device Figure 1: Connection diagram with optional extensions DALI insert Cover interface with LED Button Test DALI subscriber 3-wire extension 2-wire extension Push-button, NO contact DALI cable: type, cross-section and routing according to the specifications for 250 V cables.
  • Page 4 System 3000 Flush-mounted DALI Power control unit insert Figure 2: Terminal-specific cable cross-section: ■ When switching multiple DALI inserts in parallel, ensure correct polarity (Figure 3). Figure 3: Switching DALI inserts in parallel Parallel switched DALI inserts cannot be operated with motion or presence detector cov- ers.
  • Page 5: Technical Data

    System 3000 Flush-mounted DALI Power control unit insert The LED lights up green. The minimum brightness is stored. ■ To set the coldest colour temperature, press the button Test for less than one second. The LED lights up blue and the luminaire switches to the coldest colour temperature.
  • Page 6 Flush-mounted DALI Power control unit insert Please submit or send faulty devices postage paid together with an error description to your re- sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center. Gira Giersiepen GmbH & Co. KG...