Figure 35 - Access to Load Cable Conduit Openings (Bottom Exit Cable)
Connect Load Cables to
Current Transformers
Removable Cable Duct Boot
to load cable conduit
opening for cables exiting
from bottom power cell
4. Remove the appropriate load cable conduit openings in the top or bottom

Top Exiting Load Cables

5. Load cables for the bottom power cell should be routed first. Pull the
6. For the top power cell, pull the cables into the cabinet through the
Rockwell Automation Publication 1500-UM055H-EN-P - February 2015
of the cabinet (see
Figure 36
TIP
Follow steps 1-4 from previous section.
cables into the cabinet through the appropriate opening (see
Run the cables behind the current transformer mounting plate and into
the bottom power cell.
appropriate opening (see
Installation – Arc-Resistant Enclosure (ArcShield)
or
Figure
37).
Figure
36).
Chapter 3
Figure
36).
41