In ip20 2500 mcc style enclosure frame 13 right-side bus splice kit (6 pages)
Summary of Contents for Allen-Bradley CENTERLINE 200 A
Page 1
CENTERLINE 200/400 A Two-High Cabinet, Standard and Arc-Resistant Enclosure Bulletin Numbers 1512B, 1512BT, 1512BP, 1512DM, 1512DO, 1512M, 1562E, 1591B, 1592BF, 1592BP User Manual Original Instructions...
Page 2
CENTERLINE 200/400 A Two-High Cabinet, Standard and Arc-Resistant Enclosure User Manual Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Preface Summary of Changes This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes. Topic Page Added information around stress cones 24, 39, 46 Added 3000 A Power Splicing configuration graphic Added section on isolation switch maintenance Added attention statement around connecting arc-resistant equipment Added Appendix D, Integrated Protective Maintenance Grounding device...
Automation products in a secure system, harden the control system, manage user access, and dispose of equipment. Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and Ratings Specifications, publication IC-TD002 assemblies.
Chapter Installation – Standard Enclosure For information on the installation site preparation, see publication IMPORTANT MV-QS050. ATTENTION: Use suitable personal protective equipment (PPE) per local codes or regulations. Failure to do so may result in severe burns, injury or death. Starter Identification A structure nameplate is attached to the right-side flange of the structure (see Figure...
Chapter 1 Installation – Standard Enclosure Figure 2 - Typical Unit Nameplate Refer to these nameplates whenever you contact Rockwell Automation for assistance. Be prepared to provide such information as series number, structure series, unit series, diagram schematic and catalog number. Prepared Space When ordering a starter kit to complete a prepared space , provide the...
Chapter 1 Installation – Standard Enclosure Starter Features Provide information regarding any special features required for the starter kit. Indicate if these features are different from the motor control features in the existing, complete power cell. Recommended Torque When reinstalling components or when reassembling the cabinet, tighten the Values following bolt sizes to the specified torque values: Table 1 - Hardware Torque Values...
Chapter 1 Installation – Standard Enclosure Door Opening Procedure Opening the Low Voltage Doors Low voltage doors are identified as LV in Figure 1. To access the compartments for standard cabinets – use a flat-head screwdriver and turn both of the 1/4-turn fasteners at least 90° in a counterclockwise direction.
Page 13
Chapter 1 Installation – Standard Enclosure Figure 4 - Access to Medium Voltage Compartments Door Locking Bolts for Upper Medium Voltage Door Isolation Switch Handles Door Locking Bolts for Upper Medium Voltage Door Each medium voltage door has its own isolation switch handle and IMPORTANT interlocking safeguards.
Chapter 1 Installation – Standard Enclosure Anchoring Place the controller in the desired installation location. Use M12 (1/2 in.) floor mounting bolts to securely fasten the controller to the mounting surface. See Figure 5 as an example of the location of the mounting holes in the cabinet. Refer to Dimension Drawing provided with order documentation for additional details related to cabinet floor plan.
Chapter 1 Installation – Standard Enclosure Joining Sections Joining hardware can be found in a package mounted on the front of the shipping skid. Refer to publication MV-QS050 for level floor surface requirements. 1. Position the left side of the section on a level surface and secure the section in place with 12 mm (1/2 in.
Chapter 1 Installation – Standard Enclosure Access to the Power Bus ATTENTION: This procedure requires contact with medium voltage components. To avoid shock hazards, lock out incoming power before working on the equipment (see Power Lock-out Procedure on page 53). Verify with a hot stick or appropriate voltage measuring device that all circuits are voltage free.
Chapter 1 Installation – Standard Enclosure Figure 8 - Bus Bars from Back Access Side Access A side bus access cover is located on each side of the controller. 1. Remove the hardware from the appropriate side bus access cover (see Figure 2.
Chapter 1 Installation – Standard Enclosure Figure 9 - Side Bus Access Cover Removed Front Access– Access to Power Bus ATTENTION: To avoid shock hazards, lock out incoming power (see Power Lock-out Procedure on page 53) before working on the equipment.
Page 19
Chapter 1 Installation – Standard Enclosure Figure 10 - Center Vertical Channel Remove self-tapping screws from center vertical channel Control Wiring Harness 6. Remove each glass-polyester barrier located in front of the current transformers (see Figure 11). Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Page 20
Chapter 1 Installation – Standard Enclosure Figure 11 - Removing Glass-polyester Barrier Current Transformers Remove self-tapping screws from barrier assembly Glass-polyester barrier 7. Remove the 1/4-20 retaining screw from the cable duct barrier and remove the barrier (see Figure 12). 8.
Page 21
Chapter 1 Installation – Standard Enclosure Figure 12 - Removing Cable Duct Boot and Barrier Current Transformers CT Mounting Plate Loosen Retaining Screws Cable Duct Boot Remove Retaining Screws Cable Duct Barrier 9. To access the left side of the power bus, locate the two bus access covers at the rear, left side of the power cell.
Page 22
Chapter 1 Installation – Standard Enclosure 11. Remove the power fuses from the isolation switch. 12. Remove the interphase barriers from the trailer fuse block by raising them vertically up and out of the mounting slots (see Figure 14). 13. Use a 9/16-in. socket to remove the contactor bus bars from the isolation switch trainer fuse block.
Chapter 1 Installation – Standard Enclosure Figure 15 - Access to Right Side of Power Bus Remove self-tapping screws ATTENTION: Ensure all barriers are replaced before re-energizing the equipment. Failure to do so may result in electrical faults and cause damage to equipment or serious injury to personnel.
Chapter 1 Installation – Standard Enclosure Figure 16 - Bottom Cable Exit Configuration Cable Duct Barrier Cable Duct Boot Load Cable Connections ATTENTION: To avoid shock hazards, lock out incoming power (see Power Lock-out Procedure on page 53) before working on the equipment.
Chapter 1 Installation – Standard Enclosure Figure 17 - Access to Load Cable Conduit Openings (Top exit cable configuration shown) (LV panels removed for clarity) Remove Cable Duct Boot to access Load Cable Conduit opening for cables exiting from bottom Power Cell Current Transformer Mounting Plate Connect Load Cables to...
Page 26
Chapter 1 Installation – Standard Enclosure Figure 18 - Load Cable Conduit Openings (Top Exit Shown) Top of Cabinet Load cable Conduit Opening for cables from top power cell Load Cable Conduit opening for cables from bottom power cell Ground Lug 5.
Chapter 1 Installation – Standard Enclosure Bottom Exiting Load Cables Follow steps 1-4 from the previous section. 1. Load cables for the top power cell should be routed first. Pull the cables into the cabinet through the appropriate opening (see Figure 19).
Page 28
Chapter 1 Installation – Standard Enclosure Notes: Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Chapter Installation – Arc-Resistant Enclosure This installation section contains information on arc resistant styles of enclosures, referred to in this manual as ArcShield™. For information on the installation site preparation, see Publication IMPORTANT MV-QS050. ATTENTION: Use suitable personal protective equipment (PPE) per local codes or regulations.
Chapter 2 Installation – Arc-Resistant Enclosure Opening the Medium Voltage Doors ATTENTION: Complete the Power Lock-out procedure (see Power Lock- out Procedure on page 53) before beginning any service procedures to the unit. Failure to do so may result in severe burns, injury or death. Medium voltage doors are identified as MV in Figure Figure 21 - Access to Medium Voltage Compartments...
Chapter 2 Installation – Arc-Resistant Enclosure When closing the medium voltage door, ensure all 3/8-1.75 door IMPORTANT locking bolts on the right side of the MV door are in place and tightened until no gap between side sheet flange and door locking bolt collar.
Chapter 2 Installation – Arc-Resistant Enclosure 5. Secure the sections together using the 1/4-20 self-tapping screws (12 lb•ft [15N•m]). 6. Thread the screw through the 7 mm (0.281 in.) clearance hole to the corresponding 6 mm (0.219 in.) pilot hole. a.
Chapter 2 Installation – Arc-Resistant Enclosure Rear Access 1. Remove the hardware securing the center rear bus access cover (see Figure 25). 2. Remove the center rear bus access cover. 3. Once the rear bus cover is removed you will see the three power bus bars and ground bus (see Figure 27).
Page 35
Chapter 2 Installation – Arc-Resistant Enclosure Figure 27 - Side Bus Access Cover Ground Connection Side Bus Access Cover Ground Connection Figure 28 - ArcShield Ground Plate Removable Handle Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Chapter 2 Installation – Arc-Resistant Enclosure Front Access – Access to Power Bus ATTENTION: To avoid shock hazards, lock out incoming power (see Power Lock-out Procedure on page 53) before working on the equipment. Verify with a hot stick or appropriate voltage measuring device that all circuits are voltage free.
Page 37
Chapter 2 Installation – Arc-Resistant Enclosure 4. To access the left side of the power bus, locate the two bus access covers at the rear, left side of the power cell. Remove the four 1/4-20 self-tapping screws (12 lb•ft [15N•m]) from each cover and remove the covers (see Figure 31 on page 37).
Page 38
Chapter 2 Installation – Arc-Resistant Enclosure Figure 32 - Contactor Bus Bars (Trailer Fuse Block for Clip-on Fuses Shown) Trailer Fuse Block Mounting Bolts Contactor Bus Bars 9. Disconnect the secondary control wiring from the control power transformer (CPT) and remove the CPT mounting plate. Leave the CPT attached to the plate.
Chapter 2 Installation – Arc-Resistant Enclosure ATTENTION: Ensure all barriers are replaced before re-energizing the equipment. Failure to do so will defeat the structure’s arc resistant capabilities and result in electrical faults and cause damage to equipment or serious injury to personnel. Front Access –...
Chapter 2 Installation – Arc-Resistant Enclosure 2. Remove the cable duct boot at the top of the cabinet for top exiting load cables, or remove the one at the bottom of the cabinet for bottom exiting load cables (see Figure 35).
Page 41
Chapter 2 Installation – Arc-Resistant Enclosure Figure 36 - Load Cable Conduit Openings Load Cable Conduit Opening for Cables from Top Power Cell Top of Cabinet Load Cable Conduit Opening for Cables from Bottom Power Cell Current Transformer Mounting Plate 4.
Chapter 2 Installation – Arc-Resistant Enclosure Bottom Exiting Load Cables Follow steps 1-4 from previous section. 1. Load cables for the top power cell should be routed first. Pull the cables into the cabinet through the appropriate opening (see Figure 37).
Chapter Common Installation Bus Splicing Power Bus ATTENTION: This procedure requires contact with medium voltage components. To avoid shock hazards, lock out incoming power before working on the equipment (see Power Lock-out Procedure on page 53). Verify with a hot stick or appropriate voltage measuring device that all circuits are voltage free.
Page 44
Chapter 3 Common Installation Figure 38 - Typical 1200A Power Bus Splicing Configuration (Viewed from Front) Bus Support Bus Clamp Power Bus Splice Bar Main Horizontal Flat Washer Power Bus Hex Nut Lock Washer Figure 39 - Typical 2000A Power Bus Splicing Configuration (Viewed from Front) Bus Support Bus Clamp Power Bus...
Chapter 3 Common Installation ATTENTION: Ensure all barriers are replaced before re-energizing the equipment. Failure to do so may result in electrical faults and cause damage to equipment or severe injury to personnel. Insulated Power Bus Splicing If the starter is equipped with insulated power bus, then a splice kit with insulated links, insulating boots and tape will be provided.
Chapter 3 Common Installation Incoming Line Cable Connections ATTENTION: To avoid shock hazards, lock out incoming power (see Power Lock-out Procedure on page 53) before working on the equipment. Verify with a hot stick or appropriate voltage measuring device that all circuits are voltage free. Failure to do so may result in severe burns, injury or death.
Chapter 3 Common Installation Installation of Current Figure 43 - Current Transformer Barrier Transformer Barrier Current Barrier Transformer ATTENTION: Ensure current transformer barrier is installed before re-energizing the equipment. Failure to do so may result in electrical faults and cause damage to equipment or serious injury to personnel. Hi-Pot and Insulation Insulation integrity should be checked before energizing medium voltage electrical Resistance Test...
Chapter 3 Common Installation If an insulation resistance tester is used, it should indicate 50,000 megohms or greater if the unit is isolated from the line and the motor. If the unit is connected to a motor, the insulation resistance tester should indicate 5000 megohms or greater (phase to ground).
Chapter 3 Common Installation Typical Wiring Diagrams Figure 44 - Typical Wiring Diagram: Electrically Held Vacuum Contactor (Relay Control) 2400V-6900V,3Ø, 50/60Hz Isolating Switch Door Interlock Current Limiting Power Fuses Current Limiting Primary Fuses ____ Overload Normal Test Test Supply Point 120V 50/60Hz Main Contactor (M)
Page 50
Chapter 3 Common Installation Figure 45 - Typical Wiring Diagram: Electrically Held Vacuum Contactor (with IntelliVAC Control) 2400V-6900V,3Ø, 50/60Hz Isolating Switch Door Interlock Current Limiting Power Fuses Current Limiting Primary Fuses ____ CPT1 Overload Normal Test Extra Auxiliary Contacts K M L Test Supply Point 120V 50/60Hz...
Chapter Maintenance ATTENTION: Use suitable personal protective equipment (PPE) per local codes or regulations. Failure to do so may result in severe burns, injury or death. Establish a maintenance and inspection schedule for the IMPORTANT equipment. Annual servicing, or every 20,000 operations (whichever comes sooner) is the minimum recommended.
Chapter 4 Maintenance Door Interlock Circumvention ATTENTION: The door interlock mechanism is designed to prevent access to the medium voltage cell while the unit is energized. When the unit is in operation, do not circumvent this interlocking safety feature. Always disconnect and lock out incoming power (refer to Power Lock- out Procedure on page 53) before proceeding with any adjustments...
Chapter 4 Maintenance Power Lock-out Procedure ATTENTION: The following procedure requires moving the isolation switch handle to the ON position. To avoid shock hazards, disconnect and lock out incoming power before proceeding with servicing the equipment. Failure to lock out incoming power will result in a live power cell once the isolation switch handle is in the ON position and may cause severe burns, injury or death.
Page 54
Chapter 4 Maintenance Figure 48 - Inspecting Isolation Switch in Open Position See Detail A Grounding Bar Isolation Switch Blades must fully engage Grounding Pins of Grounding bar (Verify for each phase) Isolation Switch Shutters must be closed (Verify for each phase) Grounding Pins Detail A Isolation Switch...
Page 55
Chapter 4 Maintenance Figure 49 - Contactor Voltage Checkpoints Check line-side power here Check load-side power here 7. Use the Door Interlock Circumvention procedure (refer to Door Interlock Circumvention on page 52) to move the isolation switch handle to the ON position. 8.
Chapter 4 Maintenance Fuse Removal and Replacement ATTENTION: Only personnel who have been trained and understand the Bulletin 1500 product line are to work on this equipment. Suitable safety equipment and procedures are to be used at all times. Figure 51 - Medium Voltage Power Fuses Bolt-on Fuses Clip-on Fuse Clip-on Fuse Extractor...
Chapter 4 Maintenance ATTENTION: The fuses may be hot for up to one hour after operating. Verify the temperature before handling and use insulated hand protection if needed. Failure to do so may result in burns. Bolt-on Fuse Removal/Installation Tools required: 3/8-in. drive ratchet, 2-in. extension, 6-in. extension, 12-in. extension, 1/2-in.
Chapter 4 Maintenance Figure 52 - Clip-on Style Medium Voltage Power Fuse Blown Fuse Indicator (shown in blown state) Flare Contactor Maintenance Refer to publication 1502-UM060 for contactor maintenance instructions. Removing the Contactor ATTENTION: To avoid shock hazards, lock out incoming power (refer Power Lock-out Procedure on page 53) before working on the equipment.
Page 59
Chapter 4 Maintenance Figure 53 - Removing the Contactor (Front view) Contactor Interlock Rod Contactor Operating Level Figure 54 - Removing the Contactor (Right-side view) Contactor Interlock Rod Nylon Contactor Bushing Retaining Screw Nylon Contactor Bushing Nyloc Nut Contactor Operating Lever Contactor Remaining Tabs 8.
Chapter 4 Maintenance 11. If the contactor is being replaced with a new one, move the contactor interlock lever to the new contactor. ATTENTION: The retaining screw is critical to the mechanical integrity of the isolation switch. It is very important to ensure this screw is replaced during reassembly.
Chapter 4 Maintenance Figure 55 - Isolation Switch Handle Adjustments Isolation Switch Gap: 0.045...0.060 in. Operating Lever (1.1...1.5 mm) Switch Interlock Lever Stop Bracket Isolation Switch Handle at halfway position Contactor Interlock Rod Nyloc Nut Contactor Interlock Lever To Reduce the Gap Distance 5.
Page 62
Chapter 4 Maintenance 14. Manually close the contactor by attaching locking pliers to the contactor operating lever and pushing down until the armature plate contacts the magnetic cores (see Figure 56). Verify that the interlock lever overlaps the isolation switch operating lever by at least 3 mm (0.125 in.) (see Figure 57).
Chapter 4 Maintenance Isolation Switch Mechanism Inspection and Maintenance ATTENTION: To avoid shock hazards, lock out incoming power (refer Power Lock-out Procedure on page 53) before working on the equipment. Verify with a hot stick or appropriate voltage measuring device that all circuits are voltage free. Failure to do so may result in severe burns, injury or death.
Chapter 4 Maintenance 7. If an infrared window is not available, complete the following steps: a. Perform a visual inspection of the isolation switch. Look for dried, dark-colored, hardened grease or pitting on the incoming line stabs. A healthy isolation switch has a thin layer of clear lubricant. ATTENTION: Do not add grease.
Page 65
Chapter 4 Maintenance Figure 59 - Isolation Switch Defeater Closed position Isolation Switch Operating Handle Isolation Switch Defeater Open position 3. Phase 3 (far right linkage) must be measured for overall travel. All three phases share the same main actuating shaft but the Phase 3 is the easiest to measure.
Page 66
Chapter 4 Maintenance Figure 61 - Isolation Switch Linkage Assembly Angle Location Must have tolerance of Shaft Assembly 0/+6 degrees Red Glass Polyester Switch Link 5. Loosen the lock nuts at each clevis (Note: one is a left-handed thread). 6. Adjust the isolation switch mechanical threaded linkage with a wrench until the overall travel angle of the switch link is within the required tolerance.
Chapter 4 Maintenance If the angle is incorrect, repeat steps 5 through 7 until desired travel angle is reached. ATTENTION: All three isolation switch linkage assemblies must meet the angle tolerance requirements. Isolation Switch Mechanism Grounding Adjustment ATTENTION: To avoid shock hazards, lock out incoming power (refer Power Lock-out Procedure on page 53) before working on the equipment.
Chapter 4 Maintenance Auxiliary Contacts Inspection and ATTENTION: To avoid shock hazard, lock out incoming power (refer Replacement Power Lock-out Procedure on page 53) before working on the equipment. Verify with a hot stick or appropriate voltage measuring device that all circuits are voltage free. Failure to do so may result in severe burns, injury or death.
Chapter 4 Maintenance Isolation Switch Auxiliary The auxiliary contacts are mounted on the left side of the isolation switch, Contacts slightly below the cams on the isolation switch shaft. Normally open contacts (Isolation Switch a Contacts - ISa) are on the outside of the isolation switch housing, and normally closed contacts (Isolation Switch b Contacts - ISb) are on the inside of the housing.
Chapter 4 Maintenance Figure 66 - Adjusting Auxiliary Contacts (ISa Auxiliary Contact Shown) Gap: 0.25 in. (6.35 mm) Cam Follower Auxiliary Contact 5. Adjust the cam on the shaft so that the gap from the cam follower to the end of the cam groove is the width of the pin – 6.35 mm (0.25 in.). 6.
Chapter 4 Maintenance Adjusting the Change-of-State Point This procedure sets the secondary electrical interlock. When IMPORTANT properly adjusted, the electrical interlock is designed to open the control power circuit before the isolation switch opens as the handle is moved to the OFF position. 1.
Page 72
Chapter 4 Maintenance Figure 67 - Removing Z-clip Handle Pin Remove 1/4-20 self- tapping screws Remove Z-clip 2. Unscrew the two locking 3/8-1.75 bolts for the MV door. 3. Use a flat-headed screwdriver to turn the defeater pin on the right side of the isolation switch handle (see Figure 67).
Chapter 4 Maintenance Installing Z-clip with Isolation Switch Handle in the OFF Position 5. Reattach the Z-clip using the self-tapping screws, but do not completely tighten them. 6. Move the isolation switch handle to the OFF position. 7. Swing the door closed and inspect the position of the Z-clip with respect to the handle pin.
Chapter Spare Parts The following list of spare parts is valid for typical Bulletin 1512 and 1512BT units. Please contact your local Rockwell Automation office to ensure that the following part numbers are valid for your system. Bulletin 1512 and 1512BT Units Parts List Table 3 - Spare Parts List Recommended...
Page 76
Chapter 5 Spare Parts Notes: Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Appendix ArcShield Unit Information Overview ArcShield™ units have a robust arc resistant enclosure design that has been tested per IEEE C37.20.7 (2001). Each ArcShield structure was tested to withstand the effects of an arc flash at 40 kA for 0.5 seconds. ArcShield units provide Type 2B Accessibility.
Appendix A ArcShield Unit Information Exhaust Systems: Chimney Plenum Information or Plenum Option A plenum can be provided for each unit, and is to be field-mounted on the top of the unit structure (some incoming units may not have a plenum if top cable entry is required).
Appendix A ArcShield Unit Information Figure 70 - Cross-section of Plenum Extension, dimensions in inches [mm] 23 [584] 25 [633] Plenum Exhaust Considerations The following options for locating the plenum exhaust are presented: 1. Plenum ducted to an area of the control room where arc gases are permitted to escape, with plenum extensions (see Figure Figure 72...
Page 80
Appendix A ArcShield Unit Information Figure 71 - Plenum Exit Left with Extensions to Internal Controlled Access Area (Top View) Personnel Access Barrier Figure 72 - Plenum Exit Left with Extension(s) to Internal Controlled Access Area (Front View) Personnel Access Barrier Minimum H = 3.5 m (138 inches) Minimum L = 1.2 m (47 inches) ...
Appendix A ArcShield Unit Information Figure 73 - Chimney Exhaust Space Requirements Minimum H1: 1.7 m (67 inches) Minimum H: 1 m (39 inches) Additional Notes • The walls of the plenum exit area must be capable of withstanding the pressure generated.
Appendix A ArcShield Unit Information Each ArcShield line-up includes a chimney exhaust section that extends vertically directly above the enclosure. Chimney Exhaust Considerations 1. From the outlet of the chimney, there needs to be a minimum distance of 1.7 m (67 in.) from the top of the chimney to the ceiling, and 1 m (39 in.) on each side.
Appendix ArcShield Plenum Installation Instructions The following instructions are provided to ensure the proper installation and function of plenum components supplied with ArcShield™ enclosures. Refer to Appendix A for additional information related to ArcShield plenums before attempting to follow these instructions. Recommended Torque 1/4-20 Thread Fasteners –...
Appendix B ArcShield Plenum Installation Instructions Figure 75 - Description of Plenums and Components 18 in. wide Plenum 26 in. wide Plenum 36 in. wide Plenum Fastened directly over the 0.5 m Fastened directly over the 0.7 m Fastened directly over the 0.9 m (18 in.) wide cabinet (26 in.) wide cabinet (36 in.) wide cabinet...
Appendix B ArcShield Plenum Installation Instructions Figure 76 - ArcShield Line-up 36 in. Exhaust extension Sealed end Exhaust end Plenum exhaust can be on the left or right hand end of the line up. Pictures and figures in this procedure are shown for a right hand exhaust exit direction. Also shown is an optional vertical (top) direction exhaust extension (see Figure 88).
Page 86
Appendix B ArcShield Plenum Installation Instructions Cabinet Preparation In preparation to mount the plenum: 1. Remove the cabinet lifting means (slips of lifting angles). 2. Reinstall the 5/8-11 bolts retaining the lifting means in the holes from where they came (11 lb•ft [14.5 N•m]). Failure to install the bolts negates the cabinets ability to control any arc gases properly.
Appendix B ArcShield Plenum Installation Instructions Figure 80 - Plenum Placement Use recommended torque value for 1/4-20 fasteners Use silicone caulking generously to fill any air gaps once the Plenum has been securely mounted in place. STEP 2 – Alignment of Side- Plenums mounted side-by-side must be fastened together through the by-Side Plenums aligning holes using 5/16-in.
Appendix B ArcShield Plenum Installation Instructions IMPORTANT Any unused holes must be filled with thread forming screws. i.e.: “Lifting Lug holes”. All Gaps must be sealed and filled with silicone. STEP 3 – Sequence of Final All Plenums in a Line-up must be mounted to the top of each enclosure and to Assembly the Plenum directly beside it before the front duct sections are re-attached (see Figure...
Appendix B ArcShield Plenum Installation Instructions Figure 83 - Plenum Sections Do not re-install the front duct section of the last Plenum on the IMPORTANT exhaust side of the Line-up at this time (refer to STEP 6 – Mounting Extension/Elbow to Plenum Line-up on page 90 for more information).
Appendix B ArcShield Plenum Installation Instructions Figure 86 - 90° Elbow Section Assembly, Step 5C (Front View) The Extension components are attached to the Elbow Section using 5/16-in. Hardware. Screen Cover Plate Figure 86 illustrates what the Extension/ Elbow Assembly should resemble when finished.
Page 91
Appendix B ArcShield Plenum Installation Instructions Figure 87 - Optional Extension/Elbow with Vertical Extension (Right Side Exit) Last Plenum in line-up remains open for installation of extension assembly After the Extension/Elbow assembly is attached through the fastener holes on the inside flange of the Plenum, the front duct section can be replaced and fastened through the holes on the outside flanges.
Appendix B ArcShield Plenum Installation Instructions STEP 7 – Additional The Extension/Elbow Assembly must have additional mounting support. Mounting Support 90° Elbow Section: Approximate weight 64 kg (142 lbs) 36" Extension Assembly: Approximate weight 51 kg (112 lbs) Figure 88 shows an example of how the Extension/Elbow Sections can be supported by suspension from a high ceiling.
Appendix ArcShield Chimney Installation Instructions The following instructions are provided to ensure the proper installation and function of chimney supplied with ArcShield enclosures. Refer to Appendix A for additional information related to ArcShield chimney before attempting to follow these instructions. Recommended Torque 1/4 -20 Thread Fasteners –...
Appendix C ArcShield Chimney Installation Instructions General Plenum Layout for An example of a general chimney assembly configuration is shown in ArcShield Line-up Figure 90. Chimneys of varying widths are mounted directly over the MV enclosures of the corresponding width. Figure 90 - ArcShield Line-up with Arc Chimneys Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Appendix C ArcShield Chimney Installation Instructions Cabinet Preparation In preparation for mounting a chimney: 1. Remove the cabinet lifting means (slips of lifting angles). 2. Reinstall the 5/8-11 bolts retaining the lifting means in the holes from where they came (11 lb•ft [14.5 N•m]). Failure to reinstall the bolts negates the cabinets ability to control any arc gases properly.
Page 96
Appendix C ArcShield Chimney Installation Instructions Figure 93 - Chimney Placement Use recommended torque value for 1/4-20 fasteners Use silicone caulking generously to fill any air gaps once the chimney has been securely mounted in place. Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Appendix Integrated Protective Maintenance Grounding Device Overview The Integrated Protective Maintenance Grounding device (IPMG) is an optional feature that provides an over-center, spring loaded, snap action device that provides a low impedance grounding path for all load connections on CENTERLINE™ Bulletin 1500/1900 medium voltage motor controllers. The IPMG device can make and withstand short-circuit currents within its capabilities, from both feeding directions within the motor controller, without any latching mechanism.
Appendix D Integrated Protective Maintenance Grounding Device The compact design of the IPMG device does not compromise its rugged construction and proven performance under industrial operating conditions. Requiring minimal maintenance, this manually operated device is controlled from the outside of the standard and arc-resistant (ArcShield™) medium voltage controllers.
Appendix D Integrated Protective Maintenance Grounding Device Operating Handle IMPORTANT There must be a minimum clearance of 25.5 mm (12 in.) on the side of the cabinet where the operating handle is located. The separate operating handle is suitable for use only for the hex splined interface shaft of the IPMG device.
Page 100
Appendix D Integrated Protective Maintenance Grounding Device Figure 97 - Close the IPMG Device from an Open Position (1512B Cabinet with 400 A IPMG Device) Opening the IPMG Device from a Closed Position 1. Insert the operating handle and hex shaft, through the hole in the front of the structure.
Appendix D Integrated Protective Maintenance Grounding Device IPMG Positioning Indicators In compliance with many safety standards, such as NFPA 70E, the position of the IPMG device is seen through a standard viewing window. The Lexan viewing window is on the lower half of the main medium voltage power cell door.
Appendix D Integrated Protective Maintenance Grounding Device Key Interlocking An optional mechanical key interlock is available to lock the IPMG device in the CLOSE or OPEN positions. Contact the factory for further details. Auxiliary Switches The IPMG device comes standard with either 2-Form C auxiliary contacts or with an optional 4-Form C auxiliary contact configuration.
Appendix D Integrated Protective Maintenance Grounding Device The auxiliary contacts are factory adjusted and should not require readjustment in the field. The electrical configuration of the auxiliary contacts is shown below. Figure 100 - Standard, 2- Form C Auxiliary Contact Configuration IPMG Specifications Specifications Description...
Appendix D Integrated Protective Maintenance Grounding Device Maintenance The IPMG device is virtually maintenance free. All contacts are lubricated in the factory at the time of shipment. General annual inspections should include that the main drive line operates smoothly and does not stick or bind due to possible misalignment that is caused by the mechanical interlocks and interfacing to the main contactor and isolation switch.
Page 105
Appendix History of Changes This appendix contains the new or updated information for each revision of this publication. These lists include substantive updates only and are not intended to reflect all changes. Translated versions are not always available for each revision. Publication 1500-UM055H-EN-P - February 2015 Topic Replaced Typical Structure and Typical Nameplate graphics...
Page 106
Appendix E History of Changes Notes: Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Page 107
CENTERLINE 200/400 A Two-High Cabinet, Standard and Arc-Resistant Enclosure User Manual Rockwell Automation Publication 1500-UM055I-EN-P - December 2021...
Page 108
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, ArcShield, expanding human possibility, IntelliVAC, and Rockwell Automation are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc.
Need help?
Do you have a question about the CENTERLINE 200 A and is the answer not in the manual?
Questions and answers