Maintenance bypass
Table of Contents

Advertisement

I.
Remove all busbars from the UPS
Connect the UPS to MBP with the 'Cable to UPS1' included in the MBP's
II.
accessory
3.1.2
Mode 3-1(Dual source)
1.
Input:
I. Connect the main-ground cable (PE) to the chassis
II. Bridge the 'AC input terminal N/N' with 'busbar #1'
III. Connect the AC main source cable (N) and bypass source cable (N) with lugs
on top of each other to the aforementioned N/N terminal busbar #1
IV. Connect the 'AC input terminals mL1/mL2/mL3 to main source cable (L1/L2/L3)
V. Bridge the 'AC input terminals bL1/bL2/bL3' with 'busbar #5', then connect the
bypass source cable (L) to it
2.
Output:
I.
Connect the ground cable (PE) to the chassis
II. Bridge the 'AC segment terminal N/N' with 'busbar #1', then connect the AC
cable (N) to it