baltur BTL 14 Installation, Use And Maintenance Instruction Manual page 55

Single-stage diesel burners
Table of Contents

Advertisement

Available languages

Available languages

IRREGULARITY
Defective flame with sparks.
Flame not properly shaped with presence of
smoke and soot.
Defective flame, flickering or protruding from
combustion orifice.
Corrosion inside the boiler.
Soot at chimney outlet.
POSSIBLE CAUSE
1 Spraying pressure is too low.
2 Too much combustion air.
3 Nozzle inefficient because dirty or
worn.
4 Water in the fuel.
1 Insufficient combustion air flow.
2 Nozzle inefficient because dirty or worn.
3 Nozzle capacity too low with respect to
combustion chamber volume.
4 Combustion chamber unsuitably desi-
gned or too small.
5 Unsuitable refractory coating (it reduces
excessively the space of the flame).
6 Boiler or chimney ducts blocked.
7 Spraying pressure is low.
1 Excessive draught, only when there is
an extractor in the chimney.
2 Nozzle inefficient because dirty or worn.
3 Water in the fuel.
4 Dirty flame disk.
5 Too much combustion air.
6 Air passage between flame disk and
diffuser excessively closed.
1 Boiler operating temperature too low
(below the dew point).
2 Smoke temperature too low, approxima-
tely below 130 °C for diesel.
1 Excessive cooling of smoke (approxi-
mately below 130°C) in the chimney, for
an outside chimney not adequately heat
insulated or cold air infiltration.
25 / 28
0006080871_202001
REMEDY
1 Restore it at the required value.
2 Reduce combustion air
3 Clean or replace.
4 Drain water from the tank using a
suitable pump. Never use the burner
pump for this purpose.
1 Increase combustion air.
2 Clean or replace.
3 Decrease diesel flow rate to suit the
chamber (thermal power will obviously
be lower than necessary) or replace the
boiler.
4 Increase nozzle flow by replacing it.
5 Modify it, carefully abiding by the in-
structions given by boiler manufacturer.
6 Arrange for cleaning.
7 Restore it at the required value.
1 Adjust the suction fan speed by chan-
ging the pulley diameter.
2 Clean or replace.
3 Drain water from the tank using a sui-
table pump. Never use the burner pump
for this purpose.
4 Clean.
5 Reduce combustion air.
6 Correct the position of the combustion
head regulating device.
1 Increase the operating temperature.
2 Increase diesel flow rate is the boiler
allows it.
1 Improve insulation and close any ope-
ning letting cold air into the chimney.
ENGLISH

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Btl 20Btl 26

Table of Contents