Contents 1 Declaration of Conformity ......................1 2 Warnings........................... 2 3 About this document ........................2 4 Product information........................3 4.1 Transport and storage....................... 3 4.2 Technical data ........................4 4.2.1 Dimensions and weights, TA 450-TA 1100 ..............4 4.2.2 Dimensions and weights, TA 1400-4500 ..............5 4.2.3 Power consumption (kW)..................
1 Declaration of Conformity Manufacturer Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99 www.systemair.com hereby confirms that the following products: Air handling units: TA 450 EL 3kW 230V 1~...
Installation, operation and maintenance manual concerns air handling unit type TA, manufactured by Systemair. It consists of basic information and recommendations concerning the design, installation, start-up and operation, which shall be obeyed to ensure the proper fail-free operation of the unit.
The unit must not be put into operation before the enclosed parts are removed and installed properly. Warning The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use protective clothing. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Fig. 1 Dimensions, TA 450-1100 Dimensions in mm and weight in kg. Model H Ø Weight (kg) TA 450 EL 1125 1042 TA 650 EL 1302 1116 TA 1100 EL 1233 1146 TA 450-4500 Installation instructions Systemair Sverige AB 132615...
TA 4500 HW 1346 1006 Model Ødy Weight (kg) TA 1400 EL 1146 TA 1400 HW 1146 TA 2000 EL 1146 TA 2000 HW 1146 TA 3000 HW 1252 TA 4500 HW 1302 TA 450-4500 Installation instructions Systemair Sverige AB 132615...
TA 1400 HW 0,42 0,42 TA 2000 EL 16kW 0,71 16,0 16,71 TA 2000 EL 0,71 32,0 32,71 TA 2000 HW 0,67 0,67 TA 3000 HW 1,10 1,10 TA 4500 HW 1,90 1,90 TA 450-4500 Installation instructions Systemair Sverige AB 132615...
4.3.1 Connection box TA 450 EL Fig. 4 Connection box TA 450 EL Speed transformer Control unit Corrigo 24V Transformer Terminal block Terminal block for power input Reset button for overheat protection Circuit breaker TA 450-4500 Installation instructions Systemair Sverige AB 132615...
4.3.2 Connection box TA 650-2000 EL Fig. 5 Connection box TA 650 - 2000 EL Speed transformer Control unit Corrigo 24V Transformer Terminal block Terminal block for power input Reset button for overheat protection Circuit breaker TA 450-4500 Installation instructions Systemair Sverige AB 132615...
4.3.3 Connection box TA 1400-4500 HW Fig. 6 Connection box TA 1400-4500 HW Speed transformer Control unit Corrigo 24V Transformer Terminal block TA 450-4500 Installation instructions Systemair Sverige AB 132615...
5.1 Unpacking Verify that all ordered equipment are delivered before starting the installation. Any discrepancies from the ordered equipment must be reported to the supplier of Systemair products. 5.2 Where/how to install The outdoor air intake of the building should, if possible, be put in the northern or eastern side of the building and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets.
HW battery can easily be rotated. 5.3.1 Mounting brackets Together with the TA unit follows 4 mounting brackets that allows the unit to be mounted in accordance with figure 7 and figure 8. Fig. 8 Mounting brackets TA 450-4500 Installation instructions Systemair Sverige AB 132615...
To avoid fan noise being transferred via the ducting system, mufflers should be installed on supply air. Note: If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Cooling 0-10V DC Sensor outdoor air temp PT 1000 AI ref Sensor outdoor/extract air temp reference Sensor extract air PT 1000 * These inputs may only be wired to potential free connectors. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Cooling 0-10V DC Sensor outdoor air temp PT 1000 AI ref Sensor outdoor/extract air temp reference Sensor extract air PT 1000 * These inputs may only be wired to potential free connectors. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Alarm Output 24V AC, 0,5A Sensor outdoor air PT 1000 AI ref Sensor outdoor/extract air temp reference Sensor extract air PT 1000 * These inputs may only be wired to potential free connectors. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Alarm Output 24V AC, 0,5A Sensor outdoor air PT 1000 AI ref Sensor outdoor/extract air temp reference Sensor extract air PT 1000 * These inputs may only be wired to potential free connectors. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Default settings for high fan speed are on terminal post 230V (the single cable marked with 230V) and low fan speed on terminal post 160V (cable marked with 160V). Note: Terminal post marked 90V is not allowed to use! TA 450-4500 Installation instructions Systemair Sverige AB 132615...
400V (230V) are to be moved to the two terminal posts marked 320V (185V). * = High fan speed ** = High fan speed 400V *** = High fan speed 230 V TA 450-4500 Installation instructions Systemair Sverige AB 132615...
The extract fan must have an integrated thermal switch to protect the fan from overheating. Table 1: Available current for external extract fan (A) 1100 1400 2000 3000 4500 230 V, 1 N 0,95 400 V, 3 N 230 V, 3 N TA 450-4500 Installation instructions Systemair Sverige AB 132615...
The power demand of the electrical heating coil is controlled by a triac power regulator (Pulser) according to the desired supply air temperature that is set in the control panel. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Non-return valve Valve-actuator + water valve (accessories) Pump primary circuit The figure shows a possible solution for designing the water regulation. (a) using 2 way valve and (b) using 3 way valve. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Communication possibilities for controller E283 WEB. • RS485(Modbus): 50-51-52 or 60-61-62 • RS485(Exoline): 50-51-52-53 or 60-61-62-63 • TCP/IP Exoline • TCP/IP Modbus • TCP/IP WEB • BACnet/IP Fig. 11 BMS connection on the controller TA 450-4500 Installation instructions Systemair Sverige AB 132615...
A set of self-adhesive magnet strips are included in the package to facilitate installation on a metal surface. 8.2 Dimensions Fig. 12 Control panel dimensions Position Dimensions (mm) 115.0 94.0 26.0 c/c 60.0 50.5 TA 450-4500 Installation instructions Systemair Sverige AB 132615...
If needed, drill two holes in the wall to hang the control panel (center to center: 60 mm) (pos.1, figure 13). Fig. 13 Control panel wire connections Position Description Mounting holes Connection block Connection to brown cable Connection to yellow cable Connection to white cable Connection to black cable TA 450-4500 Installation instructions Systemair Sverige AB 132615...
• there is no unusual noise from the unit. • control panel and lamp signals are in function 10 Additional accessories For more information about silencers, diffusers/louvers, roof units, wall grilles etc., see technical catalogue and installation respective instructions. TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Page 29
TA 450-4500 Installation instructions Systemair Sverige AB 132615...
Page 30
Systemair Sverige AB reserves the right to make changes and improvements to the contents of this manual without prior notice. Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden Phone +46 222 440 00 Fax +46 222 440 99 www.systemair.com...