8.2 Operating the drive

Danger when the permissible short-circuit currents are exceeded
Serious follow-on faults are possible, if the specified short-circuit current values are exceeded.
This can result in death, serious injury or material damage.
● Observe the maximum permitted short-circuit currents and maximum specified short-circuit
Subsequent damage after a full short-circuit trip of the circuit breaker
If, after a full short-circuit trip, the circuit breaker is closed again without first checking it, the
drive or the circuit breaker can be subsequently damaged.
● Before reclosing the circuit breaker, carry out a voltage check and measure the resistance.
Damage caused by incorrect parameter assignment
Malfunctions can occur if you change parameters.
● Do not change the parameters, e.g. for the motor circuit-breaker.
Note
To complement these operating instructions, the List Manual contains an overview of all
parameters as well as a selection of function diagrams to describe the operating principle.
8.2
Operating the drive
Only trained personnel may operate the converter.
88
times.
Provide the results of these measurements to the Service & Support organization. After the
Service & Support organization has checked the values, if necessary replace the vacuum
tubes of the circuit breaker.