Siemens SINAMICS SM150 Operating Instructions Manual page 115

Medium-voltage drive
Table of Contents

Advertisement

r0046.0...26
Missing drive enable signals
A_INFMV
Display of the missing enable signals that prevent the drive control from being commissioned
Bit
Signal name
19
Internal pulse enable missing
26
Drive inactive
r0050
Active command data set (CDS)
Display of the active command data set (Command Data Set, CDS)
Bit
Signal name
00
CDS effective, bit 0
01
CDS effective, bit 1
02
CDS effective, bit 2
03
CDS effective, bit 3
You can find additional notes in the parameter description of parameters p0810, p0811, r0836 in the List Manual.
The command data set selected via the binector inputs (e.g. p0810) is displayed via r0836.
Diagnostic parameters for digital inputs/outputs
r0721
CU digital inputs, terminal actual value / CU DI terminal actual value
Displays the actual value at the digital inputs
Bit
Signal name
00
DI 0 (X122.1)
01
DI 1 (X122.2)
02
DI 2 (X122.3)
03
DI 3 (X122.4)
04
DI 4 (X132.1)
05
DI 5 (X132.2)
06
DI 6 (X132.3)
07
DI 7 (X132.4)
08
DI/DO 8 (X122.9)
09
DI/DO 9 (X122.10)
10
DI/DO 10 (X122.12)
11
DI/DO 11 (X122.13)
12
DI/DO 12 (X132.9)
13
DI/DO 13 (X132.10)
14
DI/DO 14 (X132.12)
15
DI/DO 15 (X132.13 / X131.5)
16
DI 16 (X122.5 / X120.3)
17
DI 17 (X122.6 / X120.4)
20
DI 20 (X132.5 / X120.9)
21
DI 21 (X132.6 / X120.10)
SINAMICS SM150 6SL3845-7NN42-2AA3 HBIS Shigang WRM NTM
Operating Instructions Rev.202003051222 3005356504
Operation
8.6 Fault and system messages
0 signal
1 signal
No
Yes
No
Yes
0-signal
1-signal
No
Yes
No
Yes
No
Yes
No
Yes
0 signal
1 signal
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
115