8-1-6. Monitor Function of Remote Controller Switch

Calling of sensor temperature display
The sensor temperature or operational status of
indoor unit, outdoor unit, or remote controller can be
monitored.
Monitor function
Code
Data
00
0024
Return
Procedure
1
Push the [
MENU] button to display
the menu screen.
2
Push and hold the [
and the [
to display the "Field setting menu".
→ Push and hold the buttons for more than 4
seconds.
3
Push the [
select "4. Monitor function" on the "Field
setting menu" screen, then push the "
Set" [
Set
→ Push the [
select the code to check data.
4
Push the [
CANCEL] button to return
to the "Field setting menu" screen.
MENU] button
] button at the same time
] / [
] button to
F2] button.
F2
] / [
] button to
Code
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
03
04
Indoor unit fan cumulative operating hours
F3
Indoor unit refrigerant leak detection sensor
E2
* Display and the contents
- - - - : Sensor function is not available.
0000 : Normal
0001 : Sensor has been used for 5 years.
0002 : Sensor trouble or exceeding the life of the
product for sensor
0003 : Sensor is detecting refrigerant leak
Code
60
61
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
6A
6D
Compressor cumulative operating hours
F1
– 82 –
Indoor unit data
Data name
Indoor unit heat exchanger (coil)
temperature (TCJ)
Indoor unit heat exchanger (coil)
temperature (TC)
(x1 h)
output*
Outdoor unit data
Data name
Outdoor unit heat exchanger (coil)
temperature (TE)
Outside air temperature (TO)
Heatsink temperature (THS)
Operating current (x1/10)
Outdoor heat exchange (coil)
temperature (TL)
(x100 h)