Hitachi SRW-0J Instruction Manual page 49

Remote operator
Table of Contents

Advertisement

Name
Temporary power loss
protection
Abnormal temperature
Gate Allay error
Open-phase protection
IGBT error
Thermistor error
Abnormal brake
Option 1 error 0-9
Option 2 error 0-9
During under-voltage
waiting
Chapter 10 LCD display and operating for SJ300/L300P series
Description
When an instantaneous power failure occurs for
more than 15ms, the inverter output is switched off.
Once the instantaneous power failure wait time has
elapsed and the power has not been restored it is
regarded as a normal power failure.
However, when the operation command is still ON
with restart selection the inverter will restart. So
please be careful of this.
When main circuit temperature raises by stopping of
cooling fan, the inverter output is switched off.
Communication error between CPU and gate allay
indicate
When an open-phase on the input supply occurs the
inverter output is switched off.
When an instantaneous over-current is detected on
the output the inverter output is switched off to
protect the main devices.
When the Inverter detects a high resistance on the
thermistor input from the motor the inverter output is
switched off.
When inverter cannot detect switching of the
brake(ON/FF) after releasing the brake ,and for
waiting for signal condition(b124) (When the braking
control selection(b120) is enable.)
These indicate the error of option 1. You can realize
the details each instruction manual.
These indicate the error of option 2. You can realize
the details by each instruction manual.
When the incoming voltage of the inverter has
dropped, the inverter output is switched off and the
inverter waits.
Display of remote
operator
ERR1 ***
Inst. P-F
OH. FIN
GA
PH. Fail
IGBT
TH
BRAKE
OP1-
OP1-9
OP2-
OP2-9
UV. WAIT